Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
125
15.3.7
Safety settings submenu
Safety settings
Output echo lost
Value echo lost
Navigation
Setup
Advanced setup
Safety sett.
Blocking
Navigation
Setup
Advanced setup
Safety sett.
Output echo lost
Description
Define the behavior of the output signal in case of a lost echo.
Selection
• Last valid value
• Ramp at echo lost
• Value echo lost
• Alarm
Factory setting
Last valid value
Additional information
Meaning of the options
•
Last valid value
The last valid value is kept in the case of a lost echo.
•
Ramp at echo lost
In the case of a lost echo the output value is continuously shifted towards 0 % or
100 %. The slope of the ramp is defined in the
Ramp at echo lost
parameter
•
Value echo lost
In the case of a lost echo the output assumes the value defined in the
Value
echo lost
parameter (page 125).
•
Alarm
In the case of a lost echo the device generates an alarm; see the
Failure mode
parameter (page 136).
Blocking
Navigation
Setup
Advanced setup
Safety sett.
Value echo lost
Prerequisite
Output echo lost
(page 125) =
Value echo lost
Description
Define output value in case of a lost echo.
User entry
0 to 200000.0 %
Factory setting
0.0 %
Additional information
Use the unit which has been defined for the measured value output:
• without linearization:
Level unit
• with linearization:
Unit after linearization