Pulscon LTC57 PROFIBUS PA
Operating menu
15.3.5
Linearization submenu
Linearization
Linearization type
Navigation
Setup
Advanced setup
Linearization
Blocking
Navigation
Setup
Advanced setup
Linearization
Lineariz. type
Description
Select linearization type.
Selection
• None
• Linear
• Table
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Factory setting
None
Additional information
Meaning of the options
•
None
The level is transmitted in the level unit without linearization.
•
Linear
The output value (volume/weight) is directly proportional to the level L. This is
valid, for example, for vertical cylinders. The following additional parameters
have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
•
Table
The relationship between the measured level L and the output value
(volume/weight) is given by a linearization table consisting of up to 32 pairs of
values "level - volume" or "level - weight", respectively. The following additional
parameters have to be specified:
–
Unit after linearization
–
Table mode
–
For each table point:
Level
–
For each table point:
Customer value
–
Activate table
•
Pyramid bottom
The output value corresponds to the volume or weight in a silo with pyramid
bottom. The following additional parameters have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
–
Intermediate height
(page 120): The height of the pyramid
•
Conical bottom
The output value corresponds to the volume or weight in a tank with conical
bottom. The following additional parameters have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
–
Intermediate height
(page 120): The height of the conical part of the tank