Pulscon LTC57 PROFIBUS PA
Mounting
6.2.4
Mounting the "Sensor remote" version
For the version "Probe design = Sensor remote" the following is supplied:
• The probe with the process connection
• The electronics housing
• The mounting bracket for wall or pipe mounting of the electronics housing
• The connection cable (length as ordered). The cable has got one straight and one angled
plug (90
°
). Depending on the local conditions the angled plug can be connected at the
probe or at the electronics housing.
Mounting the electronics housing
Figure 6.21
Note!
This section is only valid for devices of the version "Probe design" = "Sensor remote" (feature
"Probe design", option B).
Warning!
The plugs of the connection cable may be damaged by mechanical stress.
• Mount the probe and the electronics housing tightly before connecting the cable.
• Lay the cable such that it is not exposed to mechanical stress. Minimum bending radius:
100 mm (4 in).
• When connecting the cable: Connect the straight plug before the angled one. Torque for
both coupling nuts: 6 Nm.
Note!
If the measuring point is exposed to strong vibrations, an additional locking compound (e. g.
Loctite 243) can be applied at the plug connectors.
A
Wall mounting
B
Pipe mounting
122 (4.8)
52
(2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
50
(2
)
A
B
mm (in)