Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
139
Value 1 to 4 display
Decimal places 1 to 4
Note:
• The
Value 1 to 4 display
parameters (page 139) specify which measured
values are shown on the display and in which order.
• If more measured values are specified than the current display mode permits,
the values alternate on the device display. The display time until the next
change is configured in the
Display interval
parameter (page 140).
Blocking
Navigation
Setup
Advanced setup
Display
Value 1 display
Description
Select the measured value that is shown on the local display.
Selection
• None
a
• Level linearized
• Distance
• Current output 1
b
• Measured current
• Current output 2
• Terminal voltage
• Electronic temperature
• Analog output adv diagnostics 1
• Analog output adv diagnostics 2
a
can not be selected for the
Value 1 display
parameter
b
Visibility depends on order options or device settings
Factory setting
For level measurements
• Value 1 display: Level linearized
• Value 2 display: Distance
• Value 3 display: Current output 1
• Value 4 display: None
Blocking
Navigation
Setup
Advanced setup
Display
Decimal places 1
Description
Select the number of decimal places for the display value.
Selection
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
Factory setting
x.xx
Additional information
The setting does not affect the accuracy of the measurement or the calculations.