Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
117
Figure 15.6
Linearization types
Additional information
•
Angled bottom
The output value corresponds to the volume or weight in a silo with an angled
bottom. The following additional parameters have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
–
Intermediate height
(page 120): Height of the angled bottom
•
Horizontal cylinder
The output value corresponds to the volume or weight in a horizontal cylinder.
The following additional parameters have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
–
Diameter
•
Sphere
The output value corresponds to the volume or weight in a spherical tank. The
following additional parameters have to be specified:
–
Unit after linearization
–
Maximum value
(page 119): Maximum volume or weight
–
Diameter
A
None
B
Table
C
Pyramid bottom
D
Conical bottom
E
Angled bottom
F
Sphere
G
Horizontal cylinder
0%
100%
0%
100%
100%
0%
100%
0%
0%
100%
A
B
C/D
E
F/G