Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
E-39
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
890SD Branch Protection Fuses (North America)
It is recommended that UL Listed (JDDZ) non-renewable cartridge fuses, Class K5 or H;
or UL Listed (JDRX) renewable cartridge fuse, Class H, are installed upstream of the drive.
Model Number
Input Fuse Rating (A)
Model Number
Input Fuse Rating (A)
Constant
Quadratic
Constant
Quadratic
230VAC BUILD VARIANT
Frame B
Frame C
890SD/2/0003B 6
- 890SD/2/0024C
35 -
890SD/2/0005B 10
- 890SD/2/0030C
45 -
890SD/2/0007B 15
-
890SD/2/0011B 20
-
890SD/2/0016B 25
-
500VAC BUILD VARIANT
Frame B
Frame C
890SD/5/0002B 6
- 890SD/5/0024C
35 -
890SD/5/0003B 6
- 890SD/5/0030C
40 -
890SD/5/0004B 10
- 890SD/5/S030C
40 -
890SD/5/0006B 15
-
890SD/5/0010B 20
-
890SD/5/0012B 20
-
890SD/5/0016B 25
-
890SD/5/S0016B 25
-
Frame D
890SD/5/0039D 45
-
890SD/5/0045D 60
-
890SD/5/0059D 70
-