Programming
Page
D-216
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
92.21
SYSTEM RESET
SEQUENCING LOGIC
BOOL
0 : FALSE
1 : TRUE
FALSE ro
Output
92.22
SEQUENCER STATE
SEQUENCING LOGIC
ENUM
0 : START DISABLED
1 : START ENABLED
2 : SWITCHED ON
3 : READY
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
START
DISABLED
ro
Output
92.23
REMOTE REV OUT
SEQUENCING LOGIC
BOOL
0 : FALSE
1 : TRUE
FALSE ro
Output
92.24
HEALTHY
SEQUENCING LOGIC
BOOL
0 : FALSE
1 : TRUE
TRUE ro
Output
92.25
START DELAY
SEQUENCING LOGIC
REAL
0.000 to 30.000 s
0.000 s
rw
92.26
FAN RUNNING
SEQUENCING LOGIC
BOOL
0 : FALSE
1 : TRUE
FALSE ro
Output
93.01
ENABLE
AUTO RESTART
BOOL
0 : FALSE
1 : TRUE
FALSE rw
93.02
ATTEMPTS
AUTO RESTART
INT
1 to 10
5
rw
93.03
INITIAL DELAY 1
AUTO RESTART
REAL
0.0 to 600.0 s
10.0 s
rw
93.04
ATTEMPT DELAY 1
AUTO RESTART
REAL
0.0 to 600.0 s
10.0 s
rw
93.05
TRIGGER 1 WORD 1
AUTO RESTART
WORD
0000 to FFFF
0000
rw
93.06
TRIGGER 1 WORD 2
AUTO RESTART
WORD
0000 to FFFF
0000
rw
93.07
INITIAL DELAY 2
AUTO RESTART
REAL
0.0 to 600.0 s
0.1 s
rw
93.08
ATTEMPT DELAY 2
AUTO RESTART
REAL
0.0 to 600.0 s
0.1 s
rw
93.09
TRIGGER 2 WORD 1
AUTO RESTART
WORD
0000 to FFFF
0000
rw
93.10
TRIGGER 2 WORD 2
AUTO RESTART
WORD
0000 to FFFF
0000
rw
93.11
PENDING
AUTO RESTART
BOOL
0 : FALSE
1 : TRUE
FALSE ro
Output