Sequencing Logic
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
B-13
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Ready To Switch On
Same as the SWITCH ON ENABLE output parameter of the SEQUENCING LOGIC function block.
Switched On
Same as the SWITCHED ON output parameter of the SEQUENCING LOGIC function block.
Operation Enabled
Same as the RUNNING output parameter of the SEQUENCING LOGIC function block.
Fault
Same as the TRIPPED output parameter of the SEQUENCING LOGIC function block.
(Not) Voltage Disabled
If in Remote Comms mode, this is the same as Bit 1 of the COMMS COMMAND parameter. Otherwise it
is the same as the NOT COAST STOP input parameter of the SEQUENCING LOGIC function block.
(Not) Quick Stop
If in Remote Comms mode, this is the same as Bit 2 of the COMMS COMMAND parameter. Otherwise it
is the same as the NOT FAST STOP input parameter of the SEQUENCING LOGIC function block.
Switch On Disable
Set (=1) only when in START DISABLED state, refer to Table B-1.
Remote
This bit is set (= 1) if the Drive is in Remote mode
AND
the parameter REMOTE COMMS SEL of the
COMMS CONTROL function block is Set (= 1).