Electrical Ratings: 890CD Frame C, 380-500V
Input currents listed at 560V DC and 650V DC assuming total source impedance of 800
μ
H. Motor power, input current and
output current must not be exceeded under steady state operating conditions.
Model Number
890CD/5/0024C 890CD/5/0030C 890CD/5/S030C
Nominal Supply Voltage
560Vdc
650-705Vdc
560Vdc
650-705Vdc
560Vdc
650-705Vdc
Motor
Power
11kW 15Hp 15kW 20Hp
15kW 20Hp
External Continuous Power Rating
W
4000
4000
5000
5000
5000 5000
Vector Mode
Input
Current
A
33 28 43 36 43 36
Output Current @ 3kHz
A
24
24
30
27
30
30
Power Loss @ 3kHz
W
190
190
250
230
250
260
Output Current @ 6kHz
A
22
22
25
24
26
25
Power Loss @ 6kHz
W
200
210
280
220
290
300
Output Overload Motoring
150% overload for 60 seconds (all vector modes) 180% for 1s (V/Hz mode)
Servo Mode
Input
Current
A
27 23 36 32
43 34
Output Current @ 4kHz
A
20
20
25
22
30
28
Power Loss @ 4kHz
W
180
190
230
210
280
280
Output Current @ 8kHz
A
16
14
18
16
20
18
Power Loss @ 8kHz
W
170
170
210
220
280
290
Output Overload Motoring
200% overload for 4 seconds (PMAC mode)