21.01
V/F SHAPE
FLUXING
ENUM
0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
LINEAR LAW
rw
21.02
BASE FREQUENCY
FLUXING
REAL
7.5 to 500.0 Hz
50.0 Hz
rw
1,4
21.03
FIXED BOOST
FLUXING
REAL
0.00 to 25.00 %
0.00 %
rw
3
21.04
AUTO BOOST
FLUXING
REAL
0.00 to 25.00 %
0.00 %
rw
21.08
ACCELRTN BOOST
FLUXING
REAL
0.00 to 25.00 %
0.00 %
rw
21.09
ENERGY SAVING
FLUXING
BOOL
0 : FALSE
1 : TRUE
FALSE rw
21.10
USER FREQ 1
FLUXING
REAL
0.0 to 100.0 %
10.0 %
rw
21.11
USER VOLTAGE 1
FLUXING
REAL
0.0 to 100.0 %
10.0 %
rw
21.12
USER FREQ 2
FLUXING
REAL
0.0 to 100.0 %
20.0 %
rw
21.13
USER VOLTAGE 2
FLUXING
REAL
0.0 to 100.0 %
20.0 %
rw
21.14
USER FREQ 3
FLUXING
REAL
0.0 to 100.0 %
30.0 %
rw
21.15
USER VOLTAGE 3
FLUXING
REAL
0.0 to 100.0 %
30.0 %
rw
21.16
USER FREQ 4
FLUXING
REAL
0.0 to 100.0 %
40.0 %
rw
21.17
USER VOLTAGE 4
FLUXING
REAL
0.0 to 100.0 %
40.0 %
rw
21.18
USER FREQ 5
FLUXING
REAL
0.0 to 100.0 %
50.0 %
rw
21.19
USER VOLTAGE 5
FLUXING
REAL
0.0 to 100.0 %
50.0 %
rw
21.20
USER FREQ 6
FLUXING
REAL
0.0 to 100.0 %
60.0 %
rw
21.21
USER VOLTAGE 6
FLUXING
REAL
0.0 to 100.0 %
60.0 %
rw
21.22
USER FREQ 7
FLUXING
REAL
0.0 to 100.0 %
70.0 %
rw
21.23
USER VOLTAGE 7
FLUXING
REAL
0.0 to 100.0 %
70.0 %
rw
21.24
USER FREQ 8
FLUXING
REAL
0.0 to 100.0 %
80.0 %
rw
21.25
USER VOLTAGE 8
FLUXING
REAL
0.0 to 100.0 %
80.0 %
rw
21.26
USER FREQ 9
FLUXING
REAL
0.0 to 100.0 %
90.0 %
rw
21.27
USER VOLTAGE 9
FLUXING
REAL
0.0 to 100.0 %
90.0 %
rw