9-20
Function Parameters
AC10 Inverter
Value Function
Instructions
output. When inverter is running at 0HZ, its seen as
the running status, and ON signal is output.
15
Frequency arrival output
Indicating inverter runs at the setting target
frequency, and ON signal is output. See F312.
16
Overheat pre-alarm
Warning
When testing temperature reaches 80% of
setting value, ON signal is output. When
overheat protection occurs or testing value is
lower than 80%of setting value, ON signal stops
outputting.
17
Over latent current output
When output current of inverter reaches the
setting overlatent current, ON signal is output.
See F310 and F311.
18
Analog line disconnection
protection
Indicating inverter detects analog input lines
disconnection, and ON signal is output refer to
F741.
19
Reserved
20
Zero current detecting output
When inverter output current has fallen to zero
current detecting value, and after the setting time
of F755, ON signal is output, refer to F754 and
F755.
21
Output controlled by PC/PLC
1 means output is valid.
0 means output is invalid.
22
Reserved
23
TA\TC Output controlled by
PC/PLC
24
Watchdog token output
The token output is valid when inverter trips into
Err6.
25-29
Reserved
40
Switchover of high-frequency
performance
When this function is valid, inverter will switch
into high-frequency optimizing mode.
F307 Characteristic frequency 1
Setting range: F112
~
F111Hz
Mfr’s value: 10.00Hz
F308 Characteristic frequency 2
Mfr’s value: 50.00Hz
F309 Characteristic frequency width Setting range: 0
~
100
%
Mfr’s value: 50
When F300=2, 3, F301=2, 3 and F302=2, 3 and token characteristic frequency is selected, this
group function codes set characteristic frequency and its width. For example: setting F301=2,
F307=10, F309=10, when frequency is higher than F307, DO1 outputs ON signal. When
frequency is lower than (10-10*10%
)
=9Hz, DO1 outputs OFF signal.