15-14
Parameter Reference
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F742
Threshold of Analog Disconnected
Protection (%)
1~100
50
○
F745
Threshold of Pre-alarm Overheat (%)
0~100
80
○*
F747
Carrier Frequency Auto-adjusting
0: Invalid 1: Valid
1
√
F754
Zero-current Threshold (%)
0~200
5
╳
F755
Duration time of zero-current
0~60
0.5
√
Motor parameters: F800-F830
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F800
Motor’s Parameters Selection
Setting range:
0: Invalid;
1: Rotating tuning;
2: Stationary tuning
0
╳
F801
Rated Power
0.2
~
1000kW
○╳
F802
Rated Voltage
1
~
440V
○╳
F803
Rated Current
0.1
~
6500A
○╳
F804
Number of Motor Poles
2
~
100
4
○△
F805
Rated Rotary Speed
1
~
30000
○╳
F806
Stator Resistance
0.001
~
65.00Ω
○╳
F807
Rotor Resistance
0.001
~
65.00Ω
○╳
F808
Leakage Inductance
0.01
~
650.0mH
○╳
F809
Mutual Inductance
0.1
~
6500mH
○╳
F810
Motor Rated Power
1.00~300.0Hz
50.00
○╳
F812
Pre-exciting Time
0.000
~
3.000S
0.30
√
F813
Rotary Speed Loop KP1
0.01
~
20.00
Subject to
inverter
model
○
√
F814
Rotary Speed Loop KI1
0.01
~
2.00
Subject to
inverter
model
○
√
F815
Rotary Speed Loop KP2
0.01
~
20.00
Subject to
inverter
model
○
√
F816
Rotary Speed Loop KI2
0.01
~
2.00
Subject to
inverter
model
○
√
F817
PID Switching Frequency 1
0~F111
5.00
√
F818
PID Switching Frequency 2
F817~F111
50.00
√
F819~
F860
Reserved
Subject to
inverter
model
√
TC-Hydraulik - R