Function Parameters
9-5
AC10 Inverter
If reverse running locking is valid (F202=1), inverter has no output.
When F122=1
,
F613=1
,
F614≥2 and inverter gets forward running command and motor is rotating
in reverse, the inverter will run to 0.0Hz reverse, then run forward according to the setting value of
parameters.
If reverse running locking is valid (F202=1), whatever Flycatching is valid or not, inverter has no
output.
When F122=1
,
F613=1
,
F614≥2 and inverter gets forward running command and motor is sliding
reverse, if inverter can detect the sliding direction and track to motor speed, then inverter will run to
0.0Hz reverse, then run forward according to the setting value of parameters.
F123 Minus frequency is valid in the mode of
combined speed control.
0
:
Invalid
;
1
:
valid
0
In the mode of combined speed control, if running frequency is minus and F123=0, inverter will
run at 0Hz; if F123=1, inverter will run reverse at this frequency. (This function is controlled by
F122.)
F124 Jogging Frequency (Hz)
Setting range:
F112
~
F111
Mfr’s value: 5.00Hz
F125 Jogging Acceleration Time (S)
Setting
range:
0.1
~
3000
Mfr’s value: subject to inverter
model
F126 Jogging Deceleration Time (S)
There are two types of jogging: keypad jogging and terminal jogging. Keypad jogging is valid
only under stopped status . Carry out jogging operation through the keypad (under stopped
status):
(a) When F643=1, press the
inverter will run forward.
(b) When F643=2, press the
key,
the inverter will run reverse.
Jogging Acceleration Time: the time
for inverter to accelerate from 0Hz to
50Hz.
Jogging Deceleration Time: the time
for inverter to decelerate from 50Hz
to 0Hz.
In case of terminal jogging, make
“jogging” terminal (such as DI1) connected to CM, and inverter will run to jogging frequency.
The rated function codes are from F316 to F323.
Note: When jogging function is valid, Flycatching function is invalid.
t
f
Jogging Operation
Receiving jogging
operation instruction
R
em
ov
ing j
og
gi
ng
oper
at
ion
ins
tru
ction
F124
Figure 9-1 Jogging Operation