Parameter Reference
15-13
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
wrong
24: Communication timeout (CE)
45: Communication Timeout (CE)
46: Flycatching fault (FL)
F711
Fault Frequency of The Latest Malfunction
△
F712
Fault Current of The Latest Malfunction
△
F713
Fault PN Voltage of The Latest Malfunction
△
F714
Fault Frequency of Last Malfunction but One
△
F715
Fault Current of Last Malfunction but One
△
F716
Fault PN Voltage of Last Malfunction but One
△
F717
Fault Frequency of Last Malfunction but Two
△
F718
Fault Current of Last Malfunction but Two
△
F719
Fault PN Voltage of Last Malfunction but Two
△
F720
Record of Overcurrent Protection Fault
Times
△
F721
Record of Overvoltage Protection Fault
Times
△
F722
Record of Overheat Protection Fault Times
△
F723
Record of Overload Protection Fault Times
△
F724
Input Phase Loss
0: invalid;
1: valid
1
○
╳
F725
Reserved
F726
Overheat
0: invalid;
1: valid
1
○
╳
F727
Output Phase Loss
0: invalid;
1: valid
0
○
F728
Input Phase Loss Filtering Constant
0.1
~
60.0
5.0
√
F730
Overheat Protection Filtering Constant
0.1
~
60.0
5.0
√
F732
Voltage Threshold of Under-voltage
Protection
0~450
Subject to
inverter
model
○
F737
Over-current 1 Protection
0: Invalid
1:Valid
0
F738
Over-current 1 Protection Coefficient
0.50
~
3.00
2.50
F739
Over-current 1 Protection Record
△
F740
Reserved
F741
Analog Disconnected Protection
0: Invalid
1: Stop and AErr displays.
2: Stop and AErr is not displayed.
3: Inverter runs at the min frequency.
4: Reserved.
0
√
TC-Hydraulik - R