Parameter Reference
15-9
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F423
AO1 output range
0
:
0
~
5V
;
1
:
0
~
10V or 0-20mA
2: 4-20mA
1
√
F424
AO1 lowest corresponding frequency
0.0
~
F425
0.05Hz
√
F425
AO1 highest corresponding frequency
F424
~
F111
50.00Hz
√
F426
AO1 output compensation
0
~
120
100
√
F427-
F430
Reserved
F431
AO1 analog output signal selecting
0: Running frequency;
1: Output current;
2: Output voltage;
3: Analog AI1;
4: Analog AI2;
6: Output torque;
7: Given by PC/PLC;
8: Target frequency
0
√
F433
Corresponding current for full range of external
voltmeter
0.01
~
5.00 times of rated current
2
╳
F434
Corresponding current for full range of external
ammeter
2
╳
F435-
F436
Reserved
F437
Analog filter width
1
~
100
10
*
F438-
F459
Reserved
F460
AI1channel input mode
0: straight line mode
1: folding line mode
0
╳
F461
AI2 channel input mode
0: straight line mode
1: folding line mode
0
╳
F462
AI1 insertion point A1 voltage value
F400
~
F464
2.00V
╳
F463
AI1 insertion point A1 setting value
F401
~
F465
1.20
╳
F464
AI1 insertion point A2 voltage value
F462
~
F466
5.00V
╳
F465
AI1 insertion point A2 setting value
F463
~
F467
1.50
╳
F466
AI1 insertion point A3 voltage value
F464
~
F402
8.00V
╳
F467
AI1 insertion point A3 setting value
F465
~
F403
1.80
╳
F468
AI2 insertion point B1 voltage value
F406
~
F470
2.00V
╳
F469
AI2 insertion point B1 setting value
F407
~
F471
1.20
╳
F470
AI2 insertion point B2 voltage value
F468
~
F472
5.00V
╳
F471
AI2 insertion point B2 setting value
F469
~
F473
1.50
╳
F472
AI2 insertion point B3 voltage value
F470
~
F412
8.00V
╳
F473
AI2 insertion point B3 setting value
F471
~
F413
1.80
╳