![Parker 10G-42-0065-BF Product Manual Download Page 124](http://html.mh-extra.com/html/parker/10g-42-0065-bf/10g-42-0065-bf_product-manual_755620124.webp)
14-6
Compliance
AC10 Inverter
14.3.4 Terminal Wiring Information
Frame Size
Terminal Type
Required
Torque (in-lbs)
Wire Range
(AWG)
Wire Type
16G-31-0025-XX
16G-31-0045-XX
Input and Output
Terminal Block
10
12
STR/SOL
16G-31-0070-XX
16G-31-0100-XX
Input and Output
Terminal Block
10
10
STR/SOL
16G-11-0025-XX
16G-11-0045-XX
Input and Output
Terminal Block
10
14
STR/SOL
16G-11-0070-XX
16G-11-0100-XX
Input and Output
Terminal Block
10
14
STR/SOL
16G-41-0020-XX
16G-41-0040-XX
16G-41-0065-XX
Input and Output
Terminal Block
10
14
STR/SOL
16G-41-0080-XX
16G-41-0090-XX
Input and Output
Terminal Block
10.5
14
STR/SOL
16G-42-0120-XX
Input and Output
Terminal Block
10.5
10
STR/SOL
16G-42-0170-XX
Input and Output
Terminal Block
19
10
STR/SOL
16G-43-0230-XX
Input and Output
Terminal Block
30.4
8
STR/SOL
16G-43-0320-XX
Input and Output
Terminal Block
30.4
6
STR/SOL
Grounding – The pressure wire connector intended for connection for field installed equipment,
grounding conductor shall be plainly identified such as being marked “G”, “GRD”, “Ground”,
“Grounding”, or equivalent or with the grounding symbol (IEC 417, Symbol 5019).
TC-Hydraulik - R
ü
sdorfer Str. 8 - 25746 Heide - Lars Lornsen - T: +49 481 909 - 34 - [email protected] - www.tc-hydraulik.de