Modbus Communication
12-5
AC10 Inverter
Reading
parameter
address
Function
Remarks
100A
Read integer power value
The integer power value is read by PC.
100B
DI terminal status
DI1~DI6—bit0~bit5
100C
Terminal output status
bit0-OUT1 bit0-OUT2 bit2-fault relay
100D
AI1
0~4095 read input analog digital value
100E
AI2
0~4095 read input analog digital value
1010
Reserved
1011
0 - 10000
0 - 100.00% the percent of input pulse
1012
0 - 10000
0 – 100.00% the percent of output pulse
1013
Present-stage speed value
0000 : no function
0001 : stage speed 1
0010 : stage speed 2
0011 : stage speed 3
0100 : stage speed 4
0101 : stage speed 5
0110 : stage speed 6
0111 : stage speed 7
1000 : stage speed 8
1001 : stage speed 9
1010 : stage speed 10
1011 : stage speed 11
1100 : stage speed 12
1101 : stage speed 13
1110 : stage speed 14
1111 : stage speed 15
Monitoring in which stage speed inverter is.
1014
External counting value
Monitoring external counting value
1015
AO1
(
0~100.00
)
Monitoring analog output percent
1017
Current speed
Monitoring current speed.
1018
Read accurate power value Correct the power to 1 decimal place.