![Panduit Smartzone PViQ Connectivity System User Manual Download Page 85](http://html1.mh-extra.com/html/panduit/smartzone-pviq-connectivity-system/smartzone-pviq-connectivity-system_user-manual_3458906085.webp)
PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
84
Panel Learn Mode Method
This method may be used at initial patch field setup or when adding to a patch field that
is already setup. This method is typically used for initial patch field setup.
The following steps are used to add cross-connections to a PViQ™ Connectivity
System patch field or between two PViQ™ Connectivity System patch fields.
1. Open a supported web browser. Enter the IP address of the PViQ™ Connectivity
System that the connection is being added to.
NOTE: If you are connecting a cross-connect between two PViQ™ Connectivity
Systems, you will need to log into both systems that have an end point on that
connection to place both the end point panels into Learn mode. Follow steps 1
through 7 for each system.
2.
The Login Page will appear. Enter the appropriate username and password.
The
Dashboard page will appear.
3. Select the
Network
tab. The
Network
page will appear.
4. Select the panel from the
Select a Panel
pulldown menu.
5. Select
Learn
in the
Configuration Mode
field from the pulldown menu.
6. Click on the
Save
button to change the panel into Learn mode.
a. The Mode LED on the panel with light amber.
7. Select the other panel from the
Select a Panel
pulldown menu.
8. Select
Learn
in the
Configuration Mode
field from the pulldown menu.
9. Click on the
Save
button to change the panel to Learn mode.
a. The Mode LED on the panel will light amber.
NOTE: You must place both end point panels into Learn mode before completing the
next step (connecting the cross-connect patch cord). Learning only one end of the
connection will make that connection secure on that side and a security policy
violation on the other side.
10. Connect the cross-connect patch cord between the two ports in the patch field.
a. When you make the first connection, the LED above the port will light
amber and the system will provide a single audio beep.
b. When you make the second connection, the LED above the port will light
amber and the system will provide a single audio beep, followed quickly by