![Panduit Smartzone PViQ Connectivity System User Manual Download Page 177](http://html1.mh-extra.com/html/panduit/smartzone-pviq-connectivity-system/smartzone-pviq-connectivity-system_user-manual_3458906177.webp)
PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
176
text for the field shows:
o
Select a file that contains both a TLS Certificate and Private Key. The
SmartZone Connectivity panel manager ships with a default certificate. It is
recommended that the device administrator create a custom key/certificate pair
for each panel manager using the ECC curve SECP256R1. The PM also supports
RSA2048 keys. The key/certificate must be PEM formatted with the certificate
immediately following the key in a single file. e.g. openssl ecparam -name
SECP256R1 -genkey -param_enc explicit -out ServerKey.pem. e.g. openssl genrsa -
out ServerKey.pem 2048.
o
Note that some operating systems, such as iOS 13 and macOS Catalina
(10.15), may have additional certificate validation requirements.
•
Click “Choose File” and select the Certi Key file.
•
Click Save to upload the certificate.
•
Reboot the PViQ Panel Manager to verify the new certificate is in use.
•
Log in via https:// to the PViQ Panel Manager.
•
Navigate to the Email tab.
•
Configure Alarm Notifications to be sent using a SMTP server that provides
authentication and encryption.
o
For this example, consider a fictitious Gmail user:
Enable: Checked.
IP: 172.253.112.109
•
Note: the IP address of smtp.gmail.com may change over
time or by geographic region. You may find the IPv4 address
of the email server by using the nslookup command. E.g.
“nslookup smtp.gmail.com”.
Port: 587
Encryption Protocol: STARTTLS.
From Address: My PViQ Panel Name
Server Requires Authentication: Checked.
Username: [email protected]
Password: The password for the user. If two-factor authentication is