Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
93
24
Perform monthly test (H1)
The control unit and the installation shall be tested on a regular basis.
If one twelfth of the alarm points are tested each month, the whole
installation will be tested after one year.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S7.)
If a real fire alarm is activated, for example by
an alarm point not in
test mode
, the normal fire alarm functions will be activated, i.e. fire
alarm presentation, outputs (sounders) activated, routing equipment
(fire brigade tx) activated, etc.
See also chapter "Alphanumeric display (LCD) in EBL512", page 21.
NOTE!
If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in Win512).
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
See also chapter "Perform ZONE TEST (test mode) (H7)
"
, page 139.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Perform monthly test
ACCEPT? H1
"A"
Check that all LEDs light up!
ACCEPT
"A"
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
The buzzer (in the C.U.)
sounds and all dots in the
display are shown. All
LED:s light up, incl.
LED:s in units connected
via I/O Matrix board 4582.
When printer is available,
it will print out:
ABCDE…………Z
abcde…………z
"A"
Zone to be set in TEST MODE:
??? ??? ??? ??? Start test: ACCEPT
Write zone numbers
(e.g. 001, 002, 003,
004)
Zone to be set in TEST MODE:
001 002 003 004 Start test: ACCEPT
Press "A" to start the test
mode.