Operating Instructions Fire alarm system EBL512, V2.7.x
152
31.11
Synchronize the control units (H8/S10)
Synchronization can also be done via Win512.
The control units have to be synchronized when:
The following fault message is shown:
FAULT: CU xx has wrong information
120
During the synchronization there will be displayed information for the
control unit respectively. The information is shown on the second row
in positions 1 to 30, i.e. one position for each control unit 00-29.
-
= Synchronization not started.
X
and
?
alternating = Synchronization in progress for CU = X (X is
the last digit in the control unit number, e.g. 8 for CU no. 18 and 28).
+
= Synchronization completed
<Blank> = There is no control unit with that number in the system.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page
141.
Scroll to menu S10.
Synchronize the control units
ACCEPT? S10
"A"
Shall synchronization be started? 0
(1 = Yes, 0 = No) ACCEPT?
Press "1" and "A" to start
the synchronisation or
press "A" to go directly to
the field "Synchronization
completed" or press
"Return" to menu S10.
"1", "A"
Synchronization in progress...
0+--4+?78+??+-4 +8+0?2?+?+78+ ACCEPT?
During the synchronization
the information on each
position (on row 2) is
changing all the time. 28
CUs are shown in the
example (i.e. 15 & 16 are
not programmed). Press
"A" to continue.
"A"
Synchronization completed MM-DD HH:MM
+++++++++++++++ +++++++++++++ ACCEPT?
Month (MM), day (DD)
and time for the latest
completed synchronization
"A"
Shall synchronization be started? 0
(1 = Yes, 0 = No) ACCEPT?
Press "Return" to menu
S10. (Or press "1" and
120
If the CU restarts in conjunction with this fault, the synchronization will
start automatically otherwise it has to be started via this menu.