Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
106
25.8
Disable / Re-enable all control, exting. and
ventilation outputs (H2/B8)
Outputs
95
programmed as type 0 = control (general), type 1 = fire
ventilation and/or type 2 = extinguishing system
96
can be disabled all
at the same time.
Disabled control output
means that even if the
control expression (trigger condition) for the output respectively is
fulfilled, the output will not be activated.
Disabled control outputs are indicated by LED "Disablements" (L8)
and is shown in menu H4/U1.
The outputs in one or more control units can be disabled or the outputs
in all control units.
The outputs will be disabled until re-enabled again (
via this menu).
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B8.
Disable / Re-enable all control, exting.
and ventilation outputs ACCEPT? B8
"A"
Disable (=0) or Re-enable (=1) outputs?1
CU 99 (99 = All) ACCEPT?
Press "1" or "0", write the
CU number (or "99" for all
CUs)
97
and press "A" to
accept.
"A"
Disable / Re-enable all control, exting.
and ventilation outputs ACCEPT? B8
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.
95
Including Addressable siren 3377 and Addressable sounder base 3378.
96
Also the "Extinguish equipment output" on the German FBP interface
board 1583.
97
NOTE!
Outputs disabled for a specific control unit (e.g. CU 03) can not
be collectively re-enabled via CU 99. You have to re-enable the outputs for
the specific control unit(s), e.g. CU 03.