Operating Instructions Fire alarm system EBL512, V2.7.x
102
25.5
Re-enable zone / address (H2/B5)
Disabled alarm points, zone / addresses, are listed in menu H4/U1.
Alarm points and/or zones disabled via the function "Single
encapsulated reset" (see page 52) have to be re-enabled via this menu.
A
zone
will be displayed as ZZZ-00 (i.e. zone number and address
00).
Alarm points and/or zones disabled when the "New Zealand FB
Silence switch" (outside switch) is turned OFF, have to be re-enabled
via this menu before they can activate a new alarm.
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all alarm points / zones have been re-enabled, The LED
"Disablements" (L8) will be turned OFF, if there are no other
disablements in the system.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H2:
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B5.
Re-enable zone / address
ACCEPT? B5
"A"
Re-enable zone: 000 Address: 00
ACCEPT? L
If there are no zone /
addresses to re-enable,
menu B5 will be shown
again.
L
=a list in which
you can scroll. If it's the
correct zone / address to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone /
address and press "A" to
accept.
"A"
Re-enable zone / address
ACCEPT? B5
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.