114
27.5
Sensor values (H4/U5)
The very first week average sensor value is calculated within 2
minutes after SSD download & restart. During these 2 minutes can no
fire alarm be activated and the sensor value "000" will be shown.
The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day.
Regarding the "British Standard Marine Application" convention, see
chapter "Algorithm setting via menu H4/U5", page 117.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H4.
Present system status on display and
printer ACCEPT? H4
"A"
Disablement
Printout: (1=yes) U1
Scroll to menu U5.
Sensor values
Printout: (1=yes) U5
Press "A" (or "1") to
accept.
Here follows the
alternative "A"
(= no printout). The alternative "1" (= printout) follows below.
"A"
Start Sensor : 000000
Write the sensor's techn.
number and/or press "A"
to accept.
E.g: "000001"
Depending on
the type, the
following will
be shown:
"A"
Type 3304:
Sensor: 000001
Momentary: XX.X%/m Weekly: XX.X%/m
This is a list in which
you can scroll or use
"
" to see the next
information window
for the selected sensor.
Press "Return" to the
Start Sensor.
Scroll or write a new
techn. number or press
"Return" to menu U5.
NOTE!
XX.X%/m
= XX.X %
obscuration per meter".
XXX = sensor value.
Perf. Factor: see below
this table.
nnnnnn = algorithm short
name, see separate table,
page 115.
"
"
Sensor: 000001 Min: XX.X%/m
Perf Factor: X.XX%/m Max: XX.X%/m
"
"
Sensor: 000001
Current algorithm: nnnnnn
"A"
Type 23xx (22xx) & AUT:
Sensor: 000002
Momentary: XXX Weekly: XXX
"A"
Type 3308 / 3309:
Sensor: 000003 Min: XX°C
Momentary: XX°C Max: XX°C
"
"
Sensor: 000003
Current algorithm: nnnnnn
"A"
Type 3316:
Sensor: 00000N
Momentary: XX.X%/m Weekly: XX.X%/m
"
"
Sensor: 00000N Min: XX.X%/m
Perf Factor: X.XX%/m Max: XX.X%/m