![Panasonic EBL512 Operating Instructions Manual Download Page 131](http://html.mh-extra.com/html/panasonic/ebl512/ebl512_operating-instructions-manual_267560131.webp)
Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
129
28.4
Direction for communication on COM-/BS4-
loop (H5/A3)
NOTE!
If the selected control unit number is an
EBL512 G3
unit in
a
mixed system
the function is different, see Operating Instructions
(MEW01473) for the EBL512 G3 system.
The communication direction is normally automatically changed
every minute, to ensure that the wires are okay all the way. To make
trouble shooting easier (e.g. during the commissioning) it is possible
to lock the communication on a COM or BS4
108
loop in one direction.
FAULT: No reply techn. no. xxxxxx
will be generated with a
reduced delay time. This function can be used to list all technical
numbers "behind" a loop cut-off.
NOTE!
Loop cut-off and short-circuit faults cannot be generated,
since they require communication in both directions at the same time.
The locking only works as long as you see the text:
COM-loop is currently communicating in A-direction
(
alternatively
B-direction
)
in menu A3.
When you log out or if you are automatically logged out (after 60
min.), the communication will start in the A-direction.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
(H5)", see page 126.
Scroll to menu A3
Direction for communication on
COM-/BS4-loop ACCEPT? A3
"A"
Select type of loop: 0 (0=COM, 1=BS4)
ACCEPT?
Press "A" or "1" and "A"
to accept.
"A"
or
"1", "A"
Lock COM-loop: 0 (0-3)
Control unit: 00 ACCEPT?
Write loop number (board
number) and control unit
number. Press "A" to
accept.
Lock direction on BS4-loop: 0,
Board: 0, Control unit: 00 ACCEPT?
"A"
COM-loop is currently communicating in
A-direction
See
NOTE!
above.
(When you select a
BS4
loop, the text in this menu will still be
COM
loop).
(Maybe the B-direction is
shown instead.).
Press "A" to change
direction. Press "Return"
to finish the locking (and
return to menu A3).
"Return"
Direction for communication on
COM-/BS4-loop ACCEPT? A3
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.
108
An Autronica interface board 1584 is required in the control unit.