Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
12
3
Overview
3.1
The EBL512 system
EBL512
is a microprocessor controlled intelligent fire alarm system,
intended for analog addressable smoke detectors, as well as
conventional detectors and manual call points. Programmable control
outputs and output units are available. Up to 512 addresses can be
connected to each control unit (c.i.e.).
EBL512
is available in several types, versions and configurations. It
can be connected to a TLON network, a "system", with up to 30
control units
3
. Each control unit has access to all information.
EBL512
is designed according to the European standard EN54, part 2
and 4. The front conforms to SS3654.
3.1.1
Expansion boards
In the control unit (c.i.e.) it is possible to mount up to six expansion
boards. The following types are available:
1580
8 zones expansion board
1581
8 relays expansion board
1582
External FBP interface board
4
1583 German FBP interface board
5
1584 Autronica interface board (four BS4 loops)
6
1587
External FBP / DU interface board
4
Regarding the expansion boards, see also the EBL512 Planning
Instructions and drawings.
3.1.2
Printer
Control unit 1549 is equipped with a printer.
In control unit 1548 it is possible to mount a Printer 1558.
In Ext. Fire Brigade Panel 1826 it is possible to mount a Printer 1535.
3.1.3
Power supply
The main power source is a built-in rectifier (1537), 230 V AC, 1.5 A
/ 24 V DC, 4.5 A.
The second power source is a backup battery (2 x 12 V). In the c.i.e.
is space for two 24-27 Ah batteries. Larger batteries (up to 60 Ah)
have to be placed outside the c.i.e.
3
The control units can be EBL512 units (1548 / 1549 or 1550) with S/W
version 2.7.x and EBL512 G3 units (5000 / 5001) with S/W United version
2.7.x.
4
Max. two 1582 + 1587 boards (together) per control unit. 1582 will be
replaced by 1587.
5
Max. one 1583 board per control unit. 1583 board is
not
possible to use in
Swedish (SBF) convention.
6
Max. four 1584 boards per control unit. 1584 board is
only
possible to use
in Swedish (SBF) convention.