Operating Instructions Fire alarm system EBL512, V2.7.x
41
The buzzer in the control unit sounds 0.8 sec. each 5
th
sec.
(0.8 / 5 sec.).
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
Outputs programmed for pre-warning are activated.
44
On the first row in the c.i.e. display, the presentation number
(zone/address) is shown (for the first pre-warning).
On the second row, a user definable text message (= that for
fire alarm) will be shown (if programmed).
Example; pre-warning zone 123, address 45 (within zone 123):
Pre-warning detector 123/45
(user definable text message)
Example; pre-warning zone 123:
Pre-warning zone 123
(user definable text message)
If more than one pre-warning is generated, the LEDs "Alarms queued"
(L2) are blinking and the pre-warnings will be automatically scrolled
(each five seconds).
Pre-warning is automatically reset see chapter "Alarm reset", page 51.
15.2
Fire alarm
The system can handle up to 15360 fire alarms. Up to 512 fire alarms
will be shown in the c.i.e. display. No more fire alarms will be shown
until one or more of the 512 alarms are reset.
See also chapter "Alphanumeric display (LCD) in EBL512", page 21.
Regarding
POINT: 999-nn
(nn = 00-29, 99), see "NOTE!" at the end
of this chapter.
According to the EN54-2 standard
45
, in case of a fire alarm, the
following will happen:
The buzzer in EBL512 sounds 0.4 sec. each 0.4
th
sec. (0.4 /
0.4 sec.).
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
Output for routing equipment (Fire brigade tx) and outputs
type 4 = routing equipment are activated.
Outputs for fire alarm are activated.
46
In the c.i.e. display (and ext. FBP
47
display), the fire alarms
are presented as follows.
44
Outputs programmed for General pre-warning and outputs programmed
for the activated pre-warning(s).
45
Via Win512 can "Point alarm presentation" be selected (which is a
violation to the EN54-2 standard).
46
Outputs programmed for General fire alarm and outputs programmed for
the activated fire alarm(s).