Operating Instructions Fire alarm system EBL512, V2.7.x
70
In spite of the control unit is communicating in both directions, one or
more units cannot be found.
Check the unit's address. (DIL-Switch in some unit or with
programming tool 3314 in some units).
Faulty unit.
Detector removed from its base.
Double break on the COM / BS4 loop. (Note! Single break
gives the fault message: FAULT: Cut-off …….).
FAULT: Output unit techn. no. xxxxxx
Fault in the output unit RAM
Fault in the output unit EPROM
Fault in the output unit EEPROM ("site specific data")
Replace the output unit / output unit p.c.b.
FAULT: Printer, control unit xx
This is valid for an EBL512 G3, type 5000 with printer. Control unit
no. xx.
Faulty printer
Printer not correctly connected.
No paper.
FAULT: Read/write site data (SSW), CU xx
SSW = data that is changed during operation, i.e. sensor values, access
codes, etc.
If the C.U. was made powerless (i.e. no mains and no the
battery) without first doing a Safe shut down of control unit
via menu H8/S8 (see page 149), this fault might be generated
when the C.U. is powered again. After fault acknowledge the
SSW will get default values and the fault will be corrected
(serviced).
Some external influence has caused a fault in the SSW. This is
very serious. Call for service personnel/engineer.
FAULT: Restart CU nn code xx yyyyyyyyyy
Control unit restart has occurred. See also page 88.
nn:
Control unit number (00-29) NOTE! nn =
55
=