Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
130
28.5
Show information about Site Specific Data
(H5/A4)
Information regarding the current site specific data (SSD) is shown.
New SSD can be downloaded via a PC and Win512.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
(H5)", see page 126.
Scroll to menu A4
Show information about
site specific data ACCEPT? A4
"A"
Name: xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Downloaded: YY-MM-DD hh:mm ACCEPT?
(see NOTE! below)
YY=year, MM=month,
DD=day.
hh=hour, mm=minute
"A"
Show information about
site specific data ACCEPT? A4
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.
If there is no SSD downloaded to the control unit the following text message will be shown:
"No SSD downloaded".
NOTE!
In the "British Standard Marine Application" convention it is
possible to change the alarm algorithm for some type of analog
detectors, see chapter "Algorithm setting via menu H4/U5", page 117.
If one or more alarm algorithms are changed, the following infor-
mation will be shown instead of the information shown above:
"A"
Name: xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Modified by CU: YY-MM-DD hh:mm ACCEPT?
YY=year, MM=month,
DD=day.
hh=hour, mm=minute
If an algorithm is set (changed) via menu H4/U5, the site specific data
(SSD) in the c.i.e. is not equal to the SSD file downloaded from
Win512, i.e. a back up is required to update the SSD file
(xxxxxx.512).
"
Modified by CU
" will be changed back to "
Downloaded
" after
the next SSD download and the alarm algorithms will be according to
that SSD.
109
"Logical Name" as written in Win512 dialog box "System Properties",
tab "System Data".