Operating Instructions Fire alarm system EBL512, V2.7.x
157
32.3
Reset interlocking output (H9/C3)
All activated interlocking outputs are listed in this menu.
Interlocking output activated via its control expression and with
latching output
not selected
: The output can be reset via this menu.
Interlocking output activated via its control expression and with
latching output
selected
(in Win512): The output has to be reset via
this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.
Interlocking output activated via Web-server II: The output has to be
reset via this menu.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H9.
Interlocking outputs and inputs
ACCEPT? H9
"A"
Activated interlocking outputs/inputs
ACCEPT? C1
Scroll to menu C3.
Reset interlocking output
ACCEPT? C3
"A"
Reset interlocking output
area 000 point 00 ACCEPT?
This is a list in which you
can scroll. If there are no
activated outputs, menu C3
will be shown again.
Press "A" (for reset) or
"Return" (no reset) to
menu C3.
"A"
or
"Return"
Reset interlocking output
ACCEPT? C3
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.