Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
46
ZONE: 123 LAST: 789 No.: 003
Re-enable zone: ZZZ ACCEPT?
This is a list of disabled zones. Scroll to or write the wanted zone
number and press "A". If more zones are to be re-enabled, repeat the
procedure.
15.2.2.6
Disable / Re-enable control (X6)
ZONE: 123 LAST: 789 No.: 003
Disable/Re-enable control ACCEPT? X6
Press "A". E.g.:
ZONE: 123 LAST: 789 No.: 003
Dis(=0) or re-en(=1) control? 1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable all control, exting.
and ventilation outputs (H2/B8), page 106.
15.2.2.7
Disable / Re-enable alarm devices (X7)
ZONE: 123 LAST: 789 No.: 003
Disable/Re-enable alarm dev. ACCEPT? X7
Press "A". E.g.:
ZONE: 123 LAST: 789 No.: 003
Dis(=0) or re-en(=1) alarm dev?1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable alarm devices
(H2/B9), page 107.
15.2.3
Alert Annunciation (AA alarm)
When the
AA
function is enabled, indicated by the LED "Fire brigade
tx delay" (L16), the indications, print-outs, actions etc. are as for a
normal fire alarm
except the c.i.e. output for routing equipment
(fire brigade tx) will not be activated.
The
AA
alarm has to be
acknowledged within an acknowledge time and reset within an
investigation time, otherwise the output(s) for routing equipment (fire
brigade tx) will be activated. See EBL512 Planning Instructions for
more information regarding the
AA
function. Acknowledgement
52
and reset of the
AA
alarm can be done on a Display unit 2235
53
, an
AA
unit 1735 / 1736 or an
AA
controller 1740. See also chapter
"Alarm reset", page 51.
52
In the "Polish" (CNBOP) and "Czech" conventions, the push button
"Evacuate" (P5) can be used for "
AA
Acknowledge".
53
LED "Acknowledge" on 2235 is indicating that the push button
"Acknowledge" has been activated. A busy system can cause a time delay