background image

Panasonic Eco Solutions Nordic AB 

 

MEW01472

 

Rev:  - 

Planning Instructions  Fire alarm system EBL512 G3, United version 2.7.x 

 

57 

9.3 

Units connected to the RS232 interface J7 

9.3.1 

Web-servers 

1598

 

Web-server II.  This unit can be used: 

 

a)

  for presentation of the actual c.i.e. status in a PC using the 

web browser Microsoft Internet Explorer.  It can also send e-
mails  in  case  of  pre-warning,  fire  alarm,  fault,  disablement, 
test mode alarm and/or service signal.   

 

b)

  for  remote  control  with  encrypted  and  safe  two-way  

communication and five different user (access) levels.   

c)

  as  a  gateway  to  other  PC  systems  etc.    Three  alternatives 

are available today: 

 

        

c1)

  EBL Talk  is an  open  protocol,  used to transmit  and 

        present fire alarm information in a separate PC / system.   
        

c2)

  Tateco,  used  to  transmit  and  present  fire  alarm 

        information in an Ascom Tateco paging system. 

 

        

c3)

  SIA,  used  to  transmit  and  present  fire  alarm 

        information in a separate PC application. 

A  PC  tool, 

Web512  II  Config  tool

  version  2.7.x  is  used  for 

the configuration, which is downloaded to the web-server via 
TCP/IP. 

The  Web-server  II  consists  of  a  light  grey  plastic  cabinet 
(90x25x69.5  mm),  which  shall  be  vertically  mounted  on  the 
symmetric 35 mm DIN rail in the EBL512 G3 c.i.e.   

Web-server II has the following interfaces:  

RS232

  (PLC  COM)  to  connect  the  web-server  to  J7  in  the 

EBL512 G3 c.i.e.  

RS232

  (MODEM  COM)  to  connect  the  web-server  to  other 

PC / system 

 

RJ45

 (10 BASE-T) to connect the web-server to Internet / an 

intranet (LAN)   

Molex  3.5

  to  connect  the web-server  to  J3  (24 V  DC)  in  the 

EBL512 G3 c.i.e. 

9.4 

Other units 

9.4.1 

Alert Annunciation Controllers 

1740

 

Alert  Annunciation  Controller  (AAC).    This  unit  has  no 
display, i.e. it has to be mounted close to EBL512 G3 (or an 
ext. FBP) where the fire alarms will be presented.  
The compact size enclosure (HxWxD, 145 x 220 x 50 mm) is 
made of grey high impact ABS.  Fitted with a supplementary 
"O"  ring  gasket,  it  will  comply  with  IP61,  in  respect  of  dust 
and moisture.  The unit has no door, i.e. the front is accessed 
directly  but  the  push  buttons  are  disabled  until  they  are 
supposed  to  be  used.   

The  front's  designation  texts  are  in 

Swedish.   

Summary of Contents for EBL512 G3 5000

Page 1: ...Planning Instructions MEW01472 Revision Fire Alarm System EBL512 G3 United version 2 7 x Author Jan Pettersson Date of issue 2012 04 05 Date of rev...

Page 2: ...This page has deliberately been left blank...

Page 3: ...9 Fire Brigade Panel FBP ___________________________ 12 2 10 Control panel CP ________________________________ 12 2 11 System__________________________________________ 12 2 12 Network TLON LonWorks E...

Page 4: ...tates __________________________________ 30 6 3 8 relays expansion board 4581 _______________________ 31 6 4 I O Matrix board 4582 _____________________________ 31 6 4 1 Generic ______________________...

Page 5: ...4 unit s VO0 VO2 _________________________ 66 12 6 The 3377 unit s Output siren ________________________ 66 12 7 The 3379 unit s Output sounder _____________________ 66 12 8 The 4380 unit s Output bea...

Page 6: ...______ 94 16 9 2 2 address unit dependence ____________________ 95 16 9 3 Reset of 2 zone 2 address dependence co incidence alarm 95 16 10 Delayed alarm __________________________________ 96 16 11 Ala...

Page 7: ...115 18 Special New Zealand functions ______________ 118 18 1 Alarm devices ___________________________________ 118 18 1 1 Silence alarm devices inside switch _____________ 118 18 1 2 New Zealand FB S...

Page 8: ...open ______________________________________ 136 21 4 1 Indication door open affected by_________________ 136 21 4 2 Disablement of routing equipment _______________ 136 21 5 National holidays ________...

Page 9: ...er source _______________________ 155 26 4 Battery second power source ______________________ 155 26 5 Fuses __________________________________________ 156 26 6 Form Table of current consumption _____...

Page 10: ...Panasonic Eco Solutions Nordic AB MEW01472 Rev Planning Instructions Fire alarm system EBL512 G3 United version 2 7 x 8...

Page 11: ...y for EBL512 G3 units in a TLON Network with both EBL512 units2 and EBL512 G3 units i e a mixed network Since the EBL512 G3 control unit c i e is produced for many countries the look the texts the fun...

Page 12: ...no but sometimes a country code is added e g 5010SE a product name e g Main Board 128 alarm points a p c b number e g 9290 2B and can also have a configuration e g CFG 2 and a revision e g REV 1 some...

Page 13: ...tectors are addressable an address setting tool is used for detector types 430x An analog detector has to be plugged in an analog sensor base ASB 2 2 4 Analog Sensor Base ASB An analog detector is plu...

Page 14: ...presentation incl user definable alarm text messages if programmed 2 7 COM loop Loop a cable with two wires to which all the addressable units can be connected Starts in the c i e and it returns back...

Page 15: ...TLON Network a sub net a channel Routers are also used to increase the maximum cable length node to node in a network Router or Repeater is the same type of unit different configuration All network p...

Page 16: ...in EBL512 G3 united version 2 7 x with Win512 V2 7 x 2 18 Software S W System program The S W firmware makes the control unit the microprocessor work It is factory downloaded but a new version can via...

Page 17: ...G3 c i e Without front display and printer No door EBL512 G3 is designed according to the European standard EN54 part 2 and 4 The Swedish front conforms to SS3654 3 1 1 Printer The control unit EBL51...

Page 18: ...ting Instructions MEW01473 Drawings Normally information found in one of the documents is not found in another document i e the documents complement each other 3 4 Applications The mixed system is int...

Page 19: ...to be used to download S W Old SSD files can be opened in a newer higher version of Win512 saved edited and thereafter downloaded to an EBL512 G3 EBL512 control unit with the corresponding version 3 5...

Page 20: ...ected to the same c i e When the interlocking function is used the input the output and the Interlocking Combination area point must be in connected to one c i e An input and an output can only be use...

Page 21: ...S W version 2 7 x be the maser For more information see chapter Redundancy in distributed system in the EBL512 Planning Instruction MEW01456 NOTE EBL512 S W version 2 7 x is a special version that has...

Page 22: ...512 G3 c i e Expansion boards can be mounted option Configured for 128 256 or 512 addresses depending on the article number Printer cannot be mounted No Figure 1 Left The EBL512 G3 Control Unit 5000 w...

Page 23: ...ay the information displayed in the upper part is depending on how many alarm points zones having activated fire alarm In the middle part will the fire alarms be shown i e one alarm point or one zone...

Page 24: ...equipment Fire alarm output for Fire brigade tx and Fault condition output for Fault tx Connections and more information see dwg 512 G3 24 Battery charger Built in power supply See chapter Power suppl...

Page 25: ...ith the COM loop units in the COM loop A direction only In the B direction is only the COM loop voltage checked which has to be 12 V DC A break or short circuit on a COM loop has to generate a fault i...

Page 26: ...A direction only else the communication will be in both directions for another 10 minutes when a new cycle starts and so on Depending on if it is too low voltage on the loop short circuit one break o...

Page 27: ...1 Connections according to dwg 512 G3 23 Each output has to be programmed via Win512 version 2 7 x regarding Type of output i e output for Control Alarm devices etc Logic i e normally open NO or norma...

Page 28: ...ition output This output is normally used for fault warning routing equipment Fault tx It is a change over relay contact that is normally activated and will be de activated in case of a fault11 in the...

Page 29: ...r a special loop since the exp boards 4580 and 4581 actually are internally connected on this loop i e on COM loop 0 can in total up to six 4580 4581 and 4582 boards be used This means that for each e...

Page 30: ...The expansion board no address is set via jumpers on the expansion board respectively Board no address 4580 and 4581 4582 JP2 JP3 JP4 JP1 JP2 JP3 0 Open Open Open Open Open Open 1 Shunted Open Open Sh...

Page 31: ...It has the lowest zone line current consumption since the end of line device is a capacitor 470 nF 10 Max allowed cable resistance is 50 ohm Max allowed cable capacitance is 50 nF Total detector curre...

Page 32: ...d if this option is selected via Win512 version 2 7 x 6 2 2 5 Open circuit state The open circuit current limit15 is passed indicating no or too low zone line current consumption i e the end of line d...

Page 33: ...cation board respectively piggy back connection and has 16 switch inputs and 48 LED outputs The COM loop and 24 V DC is connected to the Application board Three different application board types can b...

Page 34: ...be used including all kinds of outputs For more information e g application board type selected via jumpers JP4 JP5 see the I O Matrix board 4582 Technical description MEW00914 Each I O Matrix board h...

Page 35: ...up to four fans Fan control panel 4593 has two Fan control application boards 4594 and two Fan control fronts see page 53 Each Fan 0 3 i e each Fan control has to be added and programmed via Win512 v...

Page 36: ...Units are connected directly in the EBL512 G3 control unit RS585 The board has to be programmed via Win512 version 2 7 x in spite of that no physical board is used regarding Address one exp board addr...

Page 37: ...the printer is mounted the checkbox Printer board connected to Main board has to be marked in the Win512 version 2 7 x Control unit properties dialog box The following will can be printed Alarms Fire...

Page 38: ...rd according to dwg 512 G3 24 8 1 Single TLON Network In a single TLON Network Network no 0 the TLON connection board 1590 5090 shall be mounted in position no 0 on the main board 8 2 Network programm...

Page 39: ...or Fault tx Also any programmable output can be used External Fire Brigade Panels and External Displays Units are connected directly to the RS485 channel More information see the Product Leaflet for t...

Page 40: ...AAFC is used on the Australian market only The I O Unit for Fan control 3361 is normally used with the Fan control panel 4593 only Discontinued units listed below can be found in old installations an...

Page 41: ...cal number NOTE COM loop address range 001 127 Name normally not changed Zone number and Address within the zone Alarm text user definable Regular Alarm algorithm some units only Options Alternative A...

Page 42: ...ing tool 3314 The base has an address label on which both the plugged in detector s COM loop address and the isolator s COM loop address can be written The Address setting tool 3314 is also used for m...

Page 43: ...20 40 65 C 2330 mode Not used in a mixed system 2312 mode This mode cannot be used for 3308 3309 Analog heat detector Enclosed IP67 24 Built in LED that is lit to indicate that the detector has gener...

Page 44: ...st cases b2 Decision algorithm Fire alarm will be activated if temperature C adjusted smoke value 27 58 Pre warning will be activated if 58 temperature C adjusted smoke value27 50 The Decision algorit...

Page 45: ...for the smoke detector set to one of six algorithms H 15 H 35 L 15 L 35 N 15 or N 35 and for the heat detector set to one of three algorithms for class A1 static response temp 54 65 C A2 S 54 70 C or...

Page 46: ...d to prevent false nuisance alarms an AI function is used i e a combined heat and smoke sensing b variable delay function c adaptive learning function See also chapter Cyber sensor functions page 122...

Page 47: ...No built in LED but terminals for an ext LED 2218 to indicate that the detector has activated a fire alarm 9 1 1 6 Accessories 3314 Address setting tool Is used to write or read the units COM loop ad...

Page 48: ...24 V DC 8 mA is required Normally low or high set via Win512 version 2 7 x The unit has two programmable relay35 outputs Relay output Re0 NC or NO contacts set via Win512 version 2 7 x Relay output R...

Page 49: ...30 sec after the Mains OK input terminal 8 goes high see below the COM loop communication is interrupted 3364 has no connection communication with the c i e The unit also has two inputs i e one for p...

Page 50: ...3312 mounted together with a sounder 3379 is mounted in the ceiling An analog detector can be plugged in the base which has screw terminals for the COM loop and an ext LED 2218 Prepared for mechanica...

Page 51: ...n analog base with a built in short circuit isolator In case of short circuit on the COM loop the number of disabled units will be minimised 4313 is power supplied via the COM loop For more informatio...

Page 52: ...oke and heat detectors shall be used else conventional units e g IS manual call point Analog addressable units are connected to a COM loop via an IS barrier unit 2842 See also drawing 512 G3 31 9 1 5...

Page 53: ...tector has generated fire alarm The function is similar to the analog photoelectric smoke detector 4301 see page 43 It has to be connected to a COM loop via an IS barrier unit 2842 ATEX class II 1 G E...

Page 54: ...label on which the programmed technical address can be written The Address setting tool 3314 is also used for the mode setting NORMAL mode Used for 3366 2330 mode Not used 2312 mode Not used 3367 Ala...

Page 55: ...S W mode settings The display and the push buttons in the unit respectively are used to set the address which also can be changed via EBL512 G3 The S W mode shall be set to xxxx 1587 xxxx type number...

Page 56: ...y in the unit The unit is power supplied from EBL512 G3 or an ext power supply The unit shall run in S W mode 1826 28 1587 Up to 1200 m cable can be used For more information see Technical description...

Page 57: ...ilt in buzzer will sound to indicate a not acknowledged AA alarm New software versions can be downloaded directly in the unit The unit is power supplied from EBL512 G3 or an external power supply The...

Page 58: ...ms will be presented in a display alpha numeric LCD 2x40 characters with back light An alarm text will also be presented together with each alarm if programmed in Win512 version 2 7 x Furthermore at l...

Page 59: ...g tool version 2 7 x is used for the configuration which is downloaded to the web server via TCP IP The Web server II consists of a light grey plastic cabinet 90x25x69 5 mm which shall be vertically m...

Page 60: ...alarm has been acknowledged The unit has the following push buttons Acknowledge used to acknowledge an AA alarm Reset used to reset an AA alarm Connections and more details are to be found in the Tech...

Page 61: ...O unit 3361 Addressable 2 voltage outputs unit 3364 9 4 6 Duct detector chambers 6377 Duct detector chamber UG 4 The housing is made of grey ABS and the venturi pipe is made of aluminium It is supplie...

Page 62: ...boxes below Figure 10 Win512 version 2 7 x Input dialog boxes Different trigger conditions require different additional information i e only the enabled fields can shall be filled in NOTE The 3361 uni...

Page 63: ...e channel per system 7 General Fire max 127 per C U 8 Activated Routing Equipment one input per C U 9 Activated Extinguishing one input per C U 10 Activated Fire Ventilation one input per C U 11 Exter...

Page 64: ...vate a fire alarm in EBL512 Zone no and Address user definable text 8 Activated Fire brigade tx feedback to the EBL512 control unit to light up the LED Fire brigade tx 50 9 Activated Extinguishing equ...

Page 65: ...tput Zone no and Address set to the same as the corresponding fire alarm from the same detector 19 Activated input will activate all programmable outputs of type Alarm devices steady continuous 20 Act...

Page 66: ...h two programmable relay outputs Re0 Re1 per unit and Addressable 2 voltage outputs units 3364 Addressable siren 3377 and Addressable sounder base 3379 can also be connected on the COM loops i e these...

Page 67: ...on board 4581 Output 0 Output 7 NOTE This board has to be programmed in Win512 version 2 7 x as a 1581 board Each 4581 board has eight programmable relay outputs Output 0 Relay output NO or NC contact...

Page 68: ...lso has one programmable special output intended for fire door closing release magnets only Output VO2 Voltage output 24 V DC max 1A54 Normally high For more information see the Technical Description...

Page 69: ...s shown in menu H9 C1 55 Controlled by menu H2 B7 Disable Re enable output type 56 Activated output is indicated by the LED Ventilation Feedback from the fire ventilation equipment to a programmable i...

Page 70: ...3 4 Time Activation Output Each output uses an Time Activation Output which controls the output s activation The following are available No 1 is default Steady Continuous No 2 is default intermittent...

Page 71: ...time when required Pulse off time when required De activation time when required Regarding the programming see chapter Time activation output page 135 Figure 13 Delay time Pulse length Pulse off and...

Page 72: ...nter locking 0 Steady continuous X X X X X X X X 1 Intermittent X X XX 2 One pulse X X 3 Steady continuous delayed activation X X X X X X X X 4 Intermittent delayed activation X X XX 5 One pulse delay...

Page 73: ...ist Depending on the selected trigger condition different arguments data have to be entered In the figure is the trigger condition General Fire Alarm selected 13 5 1 Trigger conditions Some trigger co...

Page 74: ...Zone no 23 Zone Address Disabled Zone no Address 24 General Zone Address Disabled 25 General Fault 26 General Charge Fault 27 Reset Pulse Zone Address Zone no Address 62 28 Time Channel Activated Time...

Page 75: ...n the specified interlocking area point is activated 17 One or more interlocking inputs are activated 18 One or more interlocking inputs in the specified range are activated from interlocking area no...

Page 76: ...9 32 Door open in any control unit in the system 69 33 General Key cabinet alarm For more information see EBL512 G3 United version 2 7 x Operating Instructions 34 General control disabled via menu H2...

Page 77: ...alarm or d An input with trigger condition General fire has activated fire alarm i e a fire alarm type A 74 45 Output activated when only one analog smoke or heat detector has activated fire alarm i...

Page 78: ...2 7 x 76 a b c y 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 13 5 3 2 OR a OR b OR c y y is true if at least one of the conditions a b c is true i e a 1 or b 1 or c 1 makes y 1 Th...

Page 79: ...0 0 1 1 0 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 1 13 5 3 4 Parentheses Changes priority order a OR NOT b AND c y This is same as the previous but completed with parentheses This is shown in the following tab...

Page 80: ...B8 will activate the output R1 when the door in control unit 01 is not open i e closed Example 3 Output Relay output R0 Control expression Fire Alarm Zone 145 AND Fire Alarm Zone 045 AND General Fault...

Page 81: ...d by the Validate function in Win512 version 2 7 x A Control Expression shall be programmed for the output i e for the equipment to be controlled Activated output will be indicated in menu H9 C1 Name...

Page 82: ...and the selected output and input will be shown in the Output and Input fields above It is possible to Delete an output input from the field It is possible to jump to the output and input respectively...

Page 83: ...enu H9 has the following sub menus 14 3 1 Display interlocking information H9 C1 See also chapter Interlocking indications page 81 In menu H9 C1 will information be shown as follows Interlocking area...

Page 84: ...menu 14 3 4 Disable interlocking output H9 C4 Interlocking outputs i e Output Type Interlocking can be individually disabled via menu H9 C4 NOTE Not via menu H2 B3 A disabled output will stay in or r...

Page 85: ...s involved or the COM loop involved 81 A definite time every day if programmed via Win512 version 2 7 x The output will be activated for 20 seconds Via a programmable input trigger condition Door Clo...

Page 86: ...a week average sensor value calculation 82 This is done for each analog smoke detector individually In Figure 17 the digital week average sensor values during a certain time are represented by the gra...

Page 87: ...dividual detector For an individual detector you can also get continuous information Technical no Zone Address Min Max Momentary Weekly Performance factor Also via the Web server II 1598 you can get S...

Page 88: ...different alarm algorithms are available See Figure 18 page 87 They are based on Normal N High H or Low L sensitivity Normal 15 sec or slow 35 sec detection time Normal sensitivity Default Fire alarm...

Page 89: ...from an analog smoke detector 430x this new sensor value is compared with the actual decision value and the decision value will be adjusted or not adjusted as follows If the difference between the ne...

Page 90: ...4 seconds and the step value X is according to Figure 18 but the principle is the same At start the sensor values and decision values are approx equal 10 When smoke comes into the detector the sensor...

Page 91: ...e pre warning level will be lowered to a level right between the original pre warning level and the smouldering level The fire alarm level will be lowered to a level right between the original fire al...

Page 92: ...ion value is still over the smouldering level and the pre warning level and the fire alarm level are lowered A 90 minutes timer is started 3 The decision value has here reached the pre warning level a...

Page 93: ...tector can have two alarm algorithms programmed via Win512 version 2 7 x One Regular alarm algorithm that is normally used and one Alternative alarm algorithm that is turned on off via a time channel...

Page 94: ...x min static response temperature 54 70 C The algorithm is as follows Fire alarm level is 60 C Pre warning level is 50 C Heavy heat alarm level is 90 C 16 6 3 Class B S algorithm Conforms to Class B S...

Page 95: ...be studied The sensor values are continuously picked up and evaluated by the control unit c i e for each detector individually Every value is checked if it is a new minimum or maximum value for that d...

Page 96: ...g to one of ten Two zone dependent groups 1 10 86 Function Two or more zones in the same group have to be in fire alarm state 87 at the same time to activate fire alarm in the control unit When only o...

Page 97: ...i e as follows The buzzer sounds like for pre warning 0 8 5 sec In the c i e LCD the following information is shown Co incidence alarm Zone Address ZZZ AA SMOKE User definable alarm text Menu Program...

Page 98: ...nction for each addressable multipurpose I O unit 3361 monitored Input 0 Z and 8 zones expansion board 4580 input A zone in fire alarm state will be recorded in the c i e but fire alarm will not be ac...

Page 99: ...mally turned on enabled during daytime working hours only A time channel can turn on off enable disable the AA function When the AA function is turned on enabled it is indicated by the LED Routing equ...

Page 100: ...512 version 2 7 x more than one AA alarm is allowed within that zone Number of zones can be set via Win512 version 2 7 x Normally only one zone with AA alarm is allowed but up to four zones can be all...

Page 101: ...unction see also the flow chart in the following figure One of the detectors in an AAF zone reaches its fire alarm level The AA Process starts and the AAF buzzer sounds The Acknowledgement Period star...

Page 102: ...Fire Alarm in the C I E Any detector in alarm Yes No Detector LED OFF AAFC LED OFF AAFC LED OFF Figure 23 Alarm Acknowledgement Facility AAF flow chart During the AAF Process an AAF alarm will be indi...

Page 103: ...start depending on the type of fan NOTE Normal fire alarm will not be activated Indications and actions Detector LEDs are turned on i e also a connected ext LED In the c i e display Quiet alarm detec...

Page 104: ...ultiple detector alarm The output will be activated for fire alarm from Two or more analog addressable smoke heat or multi detectors Any manual call point Any zone line input Any programmable input wi...

Page 105: ...5 Time channels can be used to disable and re enable automatically 16 16 3 Disable control output All outputs except outputs of type Alarm Device can be individually disabled via menu H2 B3 Re enabled...

Page 106: ...ime Channel is used for each external time channel which also is given a Number 15 63 The input is controlled by some external equipment e g another time system a key switch a timer etc with a normall...

Page 107: ...t After 30 seconds will also the Fire alarm output s be activated indicated by LED Fire brigade tx on the c i e front After additional 30 seconds the test will be ended and the outputs and LEDs will g...

Page 108: ...tions MEW01473 chapter Fault Programmable inputs can be used to activate fault signal in the EBL512 G3 c i e United version 2 7 x See chapter Programmable inputs page 60 16 27 Alarm texts The alarm te...

Page 109: ...e alarm Text editor The alarm text can as an alternative be typed or edited in the Win512 version 2 7 x Text editor menu Text Edit No matter where the text is typed it will be shown on both places Exp...

Page 110: ...in the Display unit D00000 for the alarm point 001 02 16 27 2 Downloading alarm texts to the DU s 1728 1735 1736 and ext FBP s 1826 1828 The texts will be downloaded when the site specific data SSD is...

Page 111: ...in power source The delay time for the fault Loss of main power source can be set in Win512 version 2 7 x to 1 300 minutes A delay time 30 minutes is a violation to the EN54 2 standard 16 29 2 LCD bac...

Page 112: ...he SSD is validated EN54 violations warnings and system errors Communication Log on Log off to the EBL512 unit Synchronize When connected and logged on to an EBL512 Synchronization of control units sa...

Page 113: ...o the EBL512 unit EBL512 settings When connected and not logged on to an EBL512 Read or download EBL512 settings to an EBL512 unit The existing EBL512 SSD can be cleared erased Advanced functions No L...

Page 114: ...e standard output for fire alarm routing equipment fire brigade tx The programmable outputs have no benefit of this function The system planner commissioner should for any output avoid such control ex...

Page 115: ...CU input in the master The output is connected like one alarm point with an end of line device Figure 26 The output for fire alarm routing equipment fire brigade tx in each slave Relay contacts shown...

Page 116: ...POINT 999 02 No 001 User definable text message The zone number 999 indicates that the fire alarm is activated by a slave The address 02 indicates the slave in this example control unit number 02 The...

Page 117: ...one 8 zones expansion board 1580 All the other control units slaves in the system connected in parallel have to be connected to one zone line input One zone line input used for this purpose on the 15...

Page 118: ...e activated111 as follows No fault on the TLON network AND fire alarm in the system or Fault on the TLON network a single open circuit cut off or single short circuit AND fire alarm activated by the c...

Page 119: ...ser definable text message may be used to indicate that the alarm originates from one or more CUs slaves Presentation of fault from several control units slaves An open circuit cut off or short circui...

Page 120: ...disabled state when you are closing the c i e door the buzzer will beep steady continuously and the message Silence switch left active will be shown in the display This message has lower priority tha...

Page 121: ...re alarm list presented in the display ALARM or ACKNOWLEDGED will be replaced with ISOLATED An example 1234567890123456789012345678901234567890 1 First alarm 002 03 Alarm number 1 of 1 2 ISOLATED alar...

Page 122: ...oltage 24 4 V generates a fault Fault message FAULT Low battery capacity If a fault is generated it will be Serviced after the 60 minutes period 18 3 Routing equipment isolate disable If any Fire alar...

Page 123: ...90123456789012345678901234567890 1 First alarm 002 03 Alarm number 1 of 1 2 ACKNOWLEDGED alarm 3 002 03 SMOKE 4 5 6 7 8 9 User definable alarm text 10 11 12 13 14 Menu Only the alarm currently shown i...

Page 124: ...4352 and 4350 uses some of the cyber sensor functions See the function respectively below The AI function is used to secure the real fire alarms but also to reduce the false nuisance alarms with up t...

Page 125: ...nter every second When T or deltaT the alarm threshold level 2 is subtracted from the counter every second 19 1 3 Pulse up down counter for smoke temperature When 2S deltaT the alarm threshold level 1...

Page 126: ...conds 4301 Fire alarm threshold level is depending on other alarm and filtering algorithms see chapter Functions Services Features page 84 4300 Fire alarm threshold level is depending on other alarm a...

Page 127: ...ck mark the Steam tobacco condition will be adapted In the example this happens in the 36h period no 10 i e after 10 x 36h 360h After the 36h period no 20 the next learning period starts again in the...

Page 128: ...nding on if and when level 1 level 2 and level 3 are exceeded or not Normal condition default or Clean condition or Steam tobacco condition and or Heating condition and or Cooking condition The follow...

Page 129: ...n value output in the NORMAL mode 4300 This detector has a smoke obscuration value output and a temperature value output in the NORMAL mode 19 7 Sensitivity compensation In order to maintain a constan...

Page 130: ...s valid for the different type of detectors 4352 This detector has no self diagnosis of internal devices 4350 This detector has self diagnosis of internal devices but no separate fault output 4301 Thi...

Page 131: ...rol unit properties 20 1 1 General data Logical name Normally not changed but can be changed when necessary Control unit number A stand alone control unit has no 00 In a system the control units are n...

Page 132: ...ntrol units and all programmable outputs in the system with trigger condition pre warning will be activated if not disabled Fire alarm will always activate all programmable outputs in the system with...

Page 133: ...and in C U 1 2 and 3 shall all fire alarms be presented How to de select a control unit Select a control unit in the Control unit drop down list box e g 1 and empty the Selected check box on the right...

Page 134: ...H4 U6 The interlocking log can be shown printed out via menu H4 U6 All three logs are circular and can show up to 999 events each 20 3 Log setup Not valid for EBL512 G3 See above 20 4 Control unit inf...

Page 135: ...etectors with this option selected via Win512 Default is 0 and up to 127 seconds can be set NOTE This delay starts when the alarm normally should have been activated i e it will be added to all other...

Page 136: ...marked Hour 00 23 Minute 00 59 21 1 6 Miscellaneous Use daylight saving time According to the current EU or country regulations see chapter Daylight saving time page 109 Use special menu during fire...

Page 137: ...ime channels can be used to disable and re enable alarm points set alert annunciation ON OFF activate programmable control outputs set alternative alarm algorithm for analog detector types 33xx 430x O...

Page 138: ...vation Delay time Can be set when required to 0 255 x 0 8 sec Pulse length Can be set when required to 0 255 x 0 8 sec Pulse off Can be set when required to 0 255 x 0 8 sec De activation Can be set wh...

Page 139: ...instead of the normal times 21 6 Alarm algorithms For each analog detector programmed via Win512 version 2 7 x is an alarm algorithm selected and when required an alternative alarm algorithm A number...

Page 140: ...1 6 2 Heat detectors 3308 3309 3316 and 4300 properties Detector 3308 AHD also valid for 3309 3316 4300 HEAT AMD i e the heat detector part when decision algorithm is not selected Logical name Class A...

Page 141: ...H 15 H 35 Offset Smouldering 18 18 15 15 12 12 18 18 15 15 12 12 Offset Pre warning 26 26 22 22 18 18 26 26 22 22 18 18 Offset Fire alarm 36 36 30 30 24 24 36 36 30 30 24 24 Level Heavy alarm 150 150...

Page 142: ...is possible Number of zones 1 1 is default 1 4 is possible Multiple alarms allowed within same zone If only one alarm point within the zone is allowed to activate alert annunciation this checkbox shal...

Page 143: ...ce function should be used Default for all zones is Group 0 no two zone dependence Click the current group number 0 for the zone to be programmed The zone number displays in the Zone box down to the r...

Page 144: ...2 G3 United version 2 7 x 142 22 Compatibility Regarding backwards compatibility Addressable short circuit isolator 4370 is compatible with Addressable short circuit isolator 4313 NOTE In system EBL51...

Page 145: ...the cable connected in the control unit returns back to the control unit In case of a break on the loop communication in two directions starts See dwg 512 G3 25 31 and 41 Cable length is depending on...

Page 146: ...2 7 x 144 23 5 Alarm device cables Alarm devices sounders etc see dwg 512 G3 23 35 and 38 ELQRB 2 x 0 6 mm 0 3 mm2 or equivalent ELQRB 10 x 2 x 1 mm 0 75 mm2 or equivalent when feeder line is require...

Page 147: ...raph 2 1 Graph with circular dots Has to be used when at least one 2335 or 3361 unit with the monitored input 0 used as a zone line input Z is used with conventional detectors e g 4350 4352 and end of...

Page 148: ...A Figure 32 Graphs showing the total conductor resistance in relation to the COM loop units total current consumption NOTE The graphs start at 0 mA but graph 1 ends at 320 mA and graph 2 ends at 350 m...

Page 149: ...r mA Figure 33 Graphs showing the cable length in relation to the COM loop units total current consumption NOTE The graphs start at 0 mA and 863 m cable length respectively but graph 1 ends at 320 mA...

Page 150: ...l state quiescent mA Alarm state active mA Control unit 5000 without printer 119 230 290 Control unit 5000 with printer 119 253 312120 Control unit 5001 grey box without front printer etc 119 179 214...

Page 151: ...put units etc Normal state quiescent mA Alarm state activated mA Addressable short circuit isolator 4370 2 2 2 2 Analog base with isolator 4313 125 1 3 1 3 Addressable zone interface 2335 5 20 Address...

Page 152: ...24 V 48 12 V 49 24 V 88 12 V Alert Annunciation unit 1735 1736 26 24 V 48 12 V 42 24 V 79 12 V External FBP 1826 1828 26 24 V 48 12 V 49 24 V 88 12 V Printer 1835 for ext FBP 1826 129 4 24 V 7 12 V 4...

Page 153: ...36 1826 1828 one 131 printer 1835 8 8 160 3 60 7 11 220 4 80 6 17 340 10 200 5 20 400 16 320 4 25 500 21 420 4 80 3 34 680 28 560 10 200 2 50 1000 42 840 16 320 1 100 max 1200 84 max 1200 18 360 Expla...

Page 154: ...f the batteries Figure 34 EBL512 G3 power supply block diagram Fuses F F1 F2 T6 3A H 250 V 5x20 mm Ceramic Batteries inside the c i e Max 28 Ah EBL512 G3 is a very flexible system i e number of and ty...

Page 155: ...26 1 2 Battery charging functions Battery charging is performed in two steps 1 Constant current The charging current is constant fixed until the battery charging voltage reaches 29 V 2 Constant voltag...

Page 156: ...on overview so that the rectifier will not be overloaded and to check calculate the required battery capacity the total EBL512 G3 current consumption excl battery charging current have to be calculate...

Page 157: ...tomer demands in normal state and in alarm state Calculate the battery capacity required in normal state QN and the battery capacity required in alarm state QA respectively QN Ah ITN A x battery backu...

Page 158: ...The relation between the total current consumption in normal state ITN and the backup time One table for the built in 28 Ah batteries and one table for the external 65 Ah batteries NOTE Theoretical va...

Page 159: ...rms tables regarding current consumption to be filled in In such a case an ampere meter shall be used to read a true value instead of a calculated current consumption A tip Turn off the main power sou...

Page 160: ...red version 5000 5001 EBL512 G3 United 2 7 0 2 7 0 4580 8 zones expansion board P c b no 9287 2B 1 0 5 1 0 2 4580 8 zones expansion board P c b no 9287 3A 2 0 4 2 0 4 4581 8 relays expansion board 1 0...

Page 161: ...to 40 Storage 40 to 70 Ambient humidity RH max 90 non condensing Ingress protection rating IP 30 Size H x W x D mm 5000 628 x 438 x 187 See also drawing 512 G3 01 5001 625 x 418 x 177 Weight kg 5000...

Page 162: ...ocking Combinations Ext faults At least 617 User definable texts can be programmed per 1728 1735 1736 1826 and 1828 unit 142 29 2 C i e System Max number of items for the system is the same as per C i...

Page 163: ...9 Disabled interlocking outputs 200150 Sensors activating SERVICE signal 100 Max number of AAF zones Max 5 detectors per AAF zone 151 100 143 Approx 1000 trigger conditions can be used in these contro...

Page 164: ...planning a fire alarm installation national regulations customer demands etc have to be followed EBL512 G3 United version 2 7 x is very flexible Many functions facilities are built in the system e g i...

Page 165: ...ions Fire alarm system EBL512 G3 United version 2 7 x 163 31 Drawings connection diagrams Resulting from continual development and improvement all dimensions quoted are approximate only and subject to...

Page 166: ...Panasonic Eco Solutions Nordic AB MEW01472 Rev Planning Instructions Fire alarm system EBL512 G3 United version 2 7 x 164 32 Revision history...

Page 167: ...This page has deliberately been left blank...

Page 168: ...Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info pewnf eu panasonic com www panasonic fire security com...

Reviews: