Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
81
Latched output
checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault
checked = Fault detection ON.
Fault Detection Time
: If the input is not activated within 5-255
seconds after the output is activated
77
, a fault will be generated:
FAULT: Interlocking input AAA/PP
14.2
Interlocking indications
One or more activated Interlocking Combinations (interlocking output
and/or input) are listed in the c.i.e. display
78
:
Disabled interlocking output is indicated by the LED "Disablements".
14.3
Information of interlocking combinations
(H9)
Menu H9 has the following sub menus.
14.3.1
Display interlocking information (H9/C1)
See also chapter "Interlocking indications", page 81.
In menu H9/C1 will information be shown as follows:
Interlocking area AAA point PP output active
User definable text message..
yyyy-mm-dd hh:mm
or
Interlocking area AAA point PP input/output active
User definable text message..
yyyy-mm-dd hh:mm
or
Interlocking area AAA point PP input active
User definable text message..
yyyy-mm-dd hh:mm
AAA = Interlocking combination Area
PP = Interlocking combination Point within the Area
Date (
yyyy-mm-dd
) and time (
hh:mm
).
Use "↑" "↓" to scroll between several interlocking combinations.
14.3.2
Activate interlocking output (H9/C2)
Even if the control expression for an interlocking output is not
fulfilled (true), the output can be manually activated via this menu.
77
After the end of the any delay time.
78
This indication has the lowest priority and will only be shown if the
display was empty.