Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
54
production put into a transparent "text slot" for the LED and
push button respectively.
All or selected alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light. An
alarm text will also be presented together with each alarm, if
programmed in Win512 version 2.7.x. Furthermore, at least
617 texts for selected fire alarms can be stored in the unit and
will in such a case be shown, instead of the texts sent from
EBL512 G3 for these alarms. These text messages will be
downloaded to the unit via Win512 version 2.7.x. A built-in
buzzer will sound like in EBL512 G3. The buzzer can be
silenced and the alarm devices in the installation can be
silenced. They will re-sound for a new alarm. When there are
queued alarms in the system, you can scroll amongst them and
they can be reset. Any fault in the system will be presented as
"General fault in system" and the buzzer will sound.
46
A
Printer 1835
can be mounted in ext. FBP 1826. It will print all
the alarms, including the alarm texts. New S/W versions can be
downloaded directly in the unit. The unit is power supplied
from EBL512 G3 or an ext. power supply.
The unit shall run in
S/W mode 1826/28 – 1587
. Up to 1200 m
cable can be used. For more information, see Technical
description MEW00249.
1828
External Fire Brigade Panel (ext. FBP). "Like" 1826 but with a
compact size enclosure (HxWxD, 145 x 220 x 50 mm) made of
grey high impact ABS. Fitted with a supplementary "O" ring
gasket, it will comply with IP61, in respect of dust and
moisture. The unit has no door, i.e. the front is accessed
directly but a key is required to get access to the push buttons.
They are disabled until they are supposed to be used. The unit
shall be wall mounted. Two compression glands are attached.
In all other respects it is like 1826, except that a printer cannot
be mounted in 1828.
The unit shall run in
S/W mode 1826/28 – 1587
. Up to 1200 m
cable can be used. For more information, see Technical
description MEW00249.
1835
Printer. Can be mounted in the External Fire Brigade Panel
1826
. It will print all the alarms, including the alarm texts.
Note that the printer current consumption is up to 200 mA when
printing.
9.2.2
Alert Annunciation Units
When the
A
lert
A
nnunciation (
AA
) function shall be used in system
EBL512 G3, a unit is required for the related manoeuvres, i.e. to
acknowledge / reset the
AA
alarms. For a detailed description of the
46
Not valid for the Swedish convention (SBF).