Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
28
NOTE! NOTE! NOTE! NOTE! NOTE!
In
Win512 version 2.7.x
the following is valid for an
EBL512 G3
control unit:
4580
boards have to be programmed as
1580
boards.
4581
boards have to be programmed as
1581
boards.
1582 boards cannot be used.
4583 / 1583 boards cannot be used.
1584 boards cannot be used.
1587
board has to be used (selected) when Display Units (1728, 1735,
1736, 1826 and 1828) shall be connected to an
EBL512 G3
control
unit United version 2.7.x. No physical board is required – the
Display Units are connected directly in the
EBL512 G3
control
unit (RS485).
6.1
Expansion board no. (address) setting
The expansion board no. (address) is set via jumpers on the expansion
board respectively.
Board no.
(address)
4580 and 4581
4582
JP2
JP3
JP4
JP1
JP2
JP3
0
Open
Open
Open
Open
Open
Open
1
Shunted
Open
Open
Shunted
Open
Open
2
Open
Shunted
Open
Open
Shunted
Open
3
Shunted
Shunted
Open
Shunted
Shunted
Open
4
Open
Open
Shunted
Open
Open
Shunted
5
Shunted
Open
Shunted
Shunted
Open
Shunted
Figure 5. Expansion boards 4580 - 4582. Jumpers for
expansion board no. (address) setting.
6.2
8 zones expansion board 4580
Each board has to be programmed
via
Win512 version 2.7.x
as a
1580
board
(4580 cannot be selected), regarding:
Address / Board no. (jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
has to be connected an end-of-line capacitor (470 nF).
Connections to "J1:1-16" and "J2" according to drawing 512 G3 - 33.