Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
114
The output for fire alarm routing equipment (fire brigade tx) in the
master will be activated
110
as follows:
Fire alarm in the system.
or
Fault
on the TLON network
AND
fire alarm activated by any
slave, which will be specially presented, see below.
or
No fault
on the TLON network
AND
fire alarm activated by
any slave
AND
no other fire alarm in the system. (In this case
also a fault will be generated, see below.)
The slave inputs in the master will be "blocked" as follows:
No fault
on the TLON network
AND
Fire alarm in the system.
Presentation of slave unit fire alarm
In the master, a fire alarm activated by a slave will be presented as in
the following example:
POINT: 999-02 No.:001
User definable text message
The zone number "999" indicates that the fire alarm is activated by a
slave. The address "02" indicates the slave, in this example control
unit number 02. The user definable text message may be used to
indicate that the alarm originates from a CU (slave).
Presentation of slave unit fault
An open circuit (cut-off) or short circuit on the slave inputs in the
master will generate a fault and a fault message as follows (depending
on which unit is used):
FAULT:Cut-off input n,1580 board b, CU xx
FAULT:Sh-circ input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.
b = 1580 board no. (0-5) in the master
xx = control unit no. (00-29) of the master.
No fault
on the TLON network
AND
fire alarm activated by any slave
AND
no other fire alarm in the system will, besides the fire alarm,
generate a fault and a fault message as follows (depending on which
unit is used):
FAULT: Alarm input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.