Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
49
connected to the COM loop but max. 10 per COM loop. Red
ABS plastic housing and PC lens. 1 Cd light output. The flash
rate is 1 Hz. An output control expression is programmed (via
Win512 version 2.7.x). For more technical data, see the
Product Leaflet.
The COM loop address is set with the Address setting tool
(3314). The beacon has an address label on which the
programmed address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode
: Used for 4380.
2330 mode
: Not used.
2312 mode
: Not used.
9.1.4
Short circuit isolators (addressable)
Each COM loop short circuit isolator
is to be programmed (via
Win512 version 2.7.x) regarding:
COM loop address
Name (Normally not changed)
Sequence Number (Serial Number in the COM loop's A-
direction.)
Connections, see dwg 512 G3 - 31. (See especially the
L
/ SA wire!)
4313
Analog base with isolator.
39
4313 is an analog base with a
built-in short circuit isolator. In case of short circuit on the
COM loop, the number of disabled units will be minimised.
4313 is power supplied via the COM loop. For more
information, see the Product Leaflet. The COM loop address is
set with the Address setting tool (3314). The unit has an
address label on which the programmed COM loop address is to
be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode
: Used for 4313 in system EBL512 G3.
2330 mode
: Used for
EBL512 G3 United version 2.7.x
in a
mixed system.
2312 mode
: Not used in a mixed system.
According to the EN54 standard, at least one short circuit isolator is
required per 32 alarm points on the COM loop. In the Australian and
New Zealand conventions at least one isolator per 40 alarm points.
Up to eight 4313 can be used, which gives nine loop segments. Each
isolator has to be given a Sequence Number, 00-07. The isolators
have to be connected consecutively (Sequence Number 00-01-02-03-
04-05-06-07) in the COM loop's A-direction.
NOTE!
EBL512 G3
has one built-in isolator in the-A direction (no. "A") and one in the B-
direction (no. "B").
39
This unit has replaced the Addr. isolator 4370.