Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
39
Address setting
Each COM loop unit has to have a unique COM loop address (001-
127). This address and the mode are set with an Address Setting Tool
(3314). For
EBL512 G3
is always the
NORMAL
mode to be used
(default).
9.1.1
Input units
Each COM loop input unit
is added and programmed via Win512
version 2.7.x. Depending on type of unit, regarding:
Technical number (NOTE! COM loop address range 001-127)
Name (normally not changed)
Zone number and Address within the zone
Alarm text (user definable)
Regular Alarm algorithm (some units only)
Options:
Alternative Alarm algorithm & Time Channel (some units only)
Alert annunciation & Time Channel (some units only)
Disablement & Time Channel (some units only)
Two-unit-dependent fire alarm, i.e. co-incidence alarm & Time
Channel (some units only)
Delayed fire alarm
Quiet alarm (Fire alarm will
not
be activated.)
Figure 7. An
example
of a Win512 version 2.7.x dialog box is
the "Analog photo electric smoke detector 3304, 4301" dialog
box.
Connections, if nothing else is specified, see drawing 512 G3 - 31.