Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
138
2300
(ION)
2210
(ION2)
2304
(OPT)
2210
(OPT2)
AUT
Offset,
Pre-warning
10
20
10
20
45
Offset,
Fire alarm
18
35
13
25
60
Offset,
Heavy smoke
22
45
22
45
100
Sampling
interval
2
2
3
3
1
NOTE! If any of these values are changed it might be a violation
to the EN54-2 standard.
Sampling interval:
1 = 3 values over alarm level to activate alarm.
2 = 5 values over alarm level to activate alarm.
3 = 7 values over alarm level to activate alarm.
21.6.2
Heat detectors' (3308, 3309, 3316 and 4300) properties
Detector
:
3308(AHD), also valid for 3309
3316 / 4300 HEAT (AMD), i.e. the heat detector part
when decision algorithm is not selected.
Logical name
: Class A1, Class A2 (S) or Class B (S).
Short name
: A1, A2 or B
Algorithm parameters
: Default values, see table:
3308 (3309)
(AHD)
3316 / 4300 HEAT
(AMD)
For 3308 (3309)
A1
A2
B
A1
A2
B
Level,
Pre-warning
92
100
128
46
50
64
x 0.5° C
Level,
Fire alarm
112
120
148
56
60
74
x 0.5° C
Level,
Heavy alarm
180
180
180
90
90
90
x 0.5° C
Rise
time
A
8
4
x 0.5° C per min.
Step
down
A
20
10
x 0.5° C
NOTE! If any of these values are changed it might be a violation
to the EN54-2 standard.
A
Rate-of-rise > 8 x 0.5 = 4° C per minute gives an alarm level
temperature step down of 20 x 0.5 = 10° C