Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
100
Quiscent state
AP timer starts
Count down
AAFC
button
pressed?
AP time
remains?
No
No
Yes
Yes
IP timer starts
Buzzer ON
Detector LED ON
AAFC LED ON
Buzzer OFF
All detectors
normal?
Count down
IP time
remains?
No
Yes
Yes
No
Fire Alarm
in the C.I.E.
Any detector
in alarm?
Yes
No
Detector LED OFF
AAFC LED OFF
AAFC LED OFF
Figure 23.
A
larm
A
cknowledgement
F
acility (AAF) flow chart.
During the
AAF Process
, an
AAF alarm
will be indicated in the c.i.e.
display ….
…. during the
A
cknowledgement
P
eriod (
A
Period):
AAF zone xx, activated
…. during the
I
nvestigation
P
eriod (
I
Period):
AAF zone xx, investigation in progress
The
AAF zone
xx (xx=00-99) is only valid for the c.i.e. it is shown in,
i.e. not for the whole system.
NOTE!
All devices belonging to an
AAF zone
must be connected to one c.i.e.