Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
43
0
10
20
30
40
50
60
70
0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60
Smoke value
T
e
m
p
e
r
a
tu
r
e
Figure 8. When the calculated value in the decision algorithm
exceeds the lower graph, pre-warning will be activated. When it
exceeds the upper graph, fire alarm will be activated.
Temperature
= °C
.
Smoke value
= obscuration (%/m) x 10
.
The Analog multi detector's COM loop address (Technical
address) is set with the Address setting tool (3314). The
detector has an address label on which the programmed
technical address can be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode
: 4300 in this mode is in Win512 version
2.7.x, for the smoke detector, set to one of six algorithms H-15,
H-35, L-15, L-35,
N-15
or N-35 and for the heat detector set to
one of three algorithms for class
A1
(static response temp. 54-
65°C), A2 S (54-70°C) or B S (69-85°C).
2330 mode
: Not used.
2312 mode
: Not used.
4301
Analog photo electric smoke detector. Scattered light (i.e.
reflection of infrared light) is used to detect smoke.
The detector has unleaded soldering.
Shall be plugged in an analog base (3312 / 3312F / 3312FL /
4313). Built-in LEDs are lit to indicate that the detector has
activated fire alarm. Prepared for mechanical lock (screw
attached) – if required.
The COM loop address is set with the Address setting tool
(3314). The detector has an address label on which the
programmed COM loop address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode
: 4301 in this mode is in Win512 version
2.7.x set to one of the six algorithms H-15, H-35, L-15, L-35,
N-15
or N-35.
2330 mode
: Not used.