Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
118
18
Special New Zealand functions
NOTE!
The functions in this chapter are valid for the
New Zealand
convention
only
.
18.1
Alarm devices
In the New Zealand convention only, the "FIRE" LEDs will indicate
steady instead of blinking when the alarm devices are disabled, see
below.
18.1.1
Silence alarm devices (inside switch)
On the c.i.e. front, the button "Silence alarm devices" (see EBL512 G3
United version 2.7.x Operating Instructions MEW01473, button "P2")
is called the "inside switch" and toggles between two states:
Alarm devices disabled
All programmable outputs of type "Alarm devices" are
disabled, i.e. they cannot be activated.
Alarm devices not disabled
All programmable outputs of type "Alarm devices" enabled,
i.e. they can be activated.
If the inside switch is in its disabled state when you are closing the
c.i.e. door the buzzer will beep steady (continuously) and the message
"
Silence switch left active
"
will be shown in the
display. This message has lower priority than fire alarms but higher
than other disablements and faults.
NOTE!
The inside switch has no function if the outside switch (see
below) is activated (on).
18.1.2
New Zealand FB Silence switch (outside switch)
The "
New Zealand FB Silence switch
" is called the "outside switch"
since it is placed outside the c.i.e. The outside switch is a key switch
and is connected to a programmable input with the trigger condition
"Silence alarms".
The outside switch is turned ON
(i.e. from not activated to activated
state).
All programmable outputs of type "Alarm devices" are
disabled
112
, i.e. they cannot be activated. The "inside switch"
(see above) has no function.
The c.i.e. built-in buzzer is silenced.
A fault is generated
113
:
"
FAULT: FB Silence switch
active, control unit xx
"
112
Indicated by LED "General disablements" on the c.i.e. front.
113
Always latched, regardless of if faults are programmed to be not latched.