Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
60
10
Programmable inputs
In each control unit are four programmable, not supervised inputs
(I0-I3) available.
On the COM loops can be connected the addressable multipurpose I/O
unit 3361 with two programmable inputs.
Each input is programmed (via Win512 version 2.7.x), see dialog
boxes below.
Figure 10. Win512 version 2.7.x "Input" dialog boxes. Different trigger conditions
require different additional information, i.e. only the enabled fields can/shall be
filled in.
NOTE!
The 3361 unit, Input 0, has a special input dialog box.
10.1
The 3361 unit's Inputs In0 / Z & In1
Connections, see drawings 512 G3 – 31 and – 36.
10.1.1
Input In0
Input 0 can be used as a general input (In0) – like the c.i.e. inputs I0-
I3
or
used as a zone line input (Z) requiring an end-of-line capacitor
(470 nF).
10.1.2
Input In1
Input 1 is an isolated optocoupler input requiring a NO / NC contact
and external 24 V DC (8 mA).