Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
25
5.3
Programmable voltage outputs (S0-S3)
The 24 V DC outputs are supervised (monitored)
7
. Connections
according to dwg 512 G3 – 23. When all connections are done a
calibration has to be performed, see chapter "Calibration of supervised
outputs", page 105 and the EBL512 G3 Operating Instructions
MEW01473, chapter "Calibration of supervised outputs (menu
H5/A1)".
Each output has to be programmed (via Win512 version 2.7.x)
regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Logic, i.e. normally low (default)
or
normally high (24 V DC)
8
.
Activation time and type (steady, pulse, delay, etc.).
Control expression (one or more trigger conditions).
See also chapter "Programmable outputs", page 64.
5.4
Programmable relay outputs (R0-R1)
Connections according to dwg 512 G3 – 23.
Each output has to be programmed (via Win512 version 2.7.x)
regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Logic, i.e. normally open (NO)
or
normally closed (NC) contacts.
Activation time and type (steady, pulse, delay, etc.).
Control expression (one or more trigger conditions).
See also chapter "Programmable outputs", page 64.
5.5
Programmable inputs (I0-I3)
Connections according to dwg 512 G3 – 23.
Each input has to be programmed (via Win512 version 2.7.x)
regarding:
Trigger condition (Triggered by).
Logic, i.e. normally open (NO)
or
normally closed (NC) contacts.
Additional information, depending on the selected trigger
condition (Fault no., Zone, Address, Fault message (Error text),
etc.)
Open = R > 20K. Closed = R < 500
.
An input has to be activated > 0.5 sec.
See also chapter "Programmable inputs", page 60.
7
The outputs are in Win512 version 2.7.x default set as supervised but via
Win512 version 2.7.x it is possible to set each output (S0-S3) individually to
be not supervised.
8
A normally high output is not supervised.