Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
Strategy
Name
Information text
Unit
St-SP Min.
Max. Remark
Strategy
(only when more than 1 HP in system)
leading
Lead change
1
0
1 Running time-dependent lead change? 0: no;
1: yes
running time
Change in lead after running
time
h
100
10 10,000 Running time difference for switching the lead
sequHC
Heat source - sequence
heating
321
1
321 Sequence (prior to running time switchover),
2 HPs = 21, 12; 3 HPs = 312, 231, 213, 132,
123... possible.
sequDHW
Heat source - sequence
domestic hot water
1
1
321 Sequence (prior to running time switching),
2 HPs = 2, 12; 21; 3 HPs = 312, 231, 213, 132,
123... possible.
Buffer tank
Name
Information text
Unit
St-SP Min.
Max. Remark
Buffer tank
boostZ1
Boost demand buffer zone1
°C
2.0
0.0
25.0 Demand of heating circuit is increased (heat-
ing) / reduced (cooling) by set value