21
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Easy Setup Overview
3
Continue Step 9
Perform settings for “Solar Domestic hot water tank” (if available)
Name
Information text
Standard
setpoint
Remark
9-7
solColl
Solar collector temp.
0
Assign available input terminal
(17 - 24) e.g. terminal 24;
9-8
solTank
Solar tank temp.
0
optional: assign solar buffer sensor
(otherwise: DHW tank sensor);
Assign terminal
9-9
solPu
Solar pump
0
assign available output terminal: e.g.
terminal 9
9-10
TDiffSolOn
Temp. difference solar pump
on
8.0 K
9-11
TDiffSolOff
Temp. difference solar pump
off
2.0 K
9-12
maxTSolTa
max. temperature Sol.-tank
sensor
70.0 °C
9-13
maxTcoll
max. temperature collector
sensor
110.0 °C
9-14
collFrLim
Frost.lim collector
–10.0 °C
→
Domestic hot water Solar, P. 82
Perform settings for “Solar Buffer tank” (if available)
Name
Information text
Standard
setpoint
Remark
9-15
solColl
Solar collector temp.
0
Assign available input terminal (17 -
24) e.g. terminal 24;
9-16
solPu
Solar pump
0
assign available output terminal: e.g.
terminal 9
9-17
tDiffOn
Temp. difference solar on
8.0 K
9-18
tDiffOff
Temp. difference solar off
2.0 K
9-19
maxTsolar
max. temp. Solar circuit
90.0 °C
9-20
solFrLim
Frost limit
–10.0 °C
→
Buffer Solar, P. 83
9
Summary of Contents for Aquarea PAW-HPM1
Page 2: ...Notes ...