104
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
►
Press the
[▲]
button to return to the basic display.
►
Press the
[OK]
button to open the menu structure.
►
With the
[▼]
and
[OK]
buttons, open in the
MCR-BMS
menu for the respective
control circuit the sub-menu
manual operation
(Example: Sub-menu
MCR-
BMS» heatCirc. » heatC. 1 » manual operation
)
►
In the
manual operation
sub-menu, manually control the assigned actuators
and check their function.
(The function of the parameter values for manual operation of the valves and
pumps is described in the following table)
►
After successful check of all manual operation commands in the control circuits,
reset to automatic (parameter value
3
).
►
Open the menu for the operating mode switch , and set the operating mode
switch of the controller to
Auto
.
The function check for the outputs is complete.
Meaning of the parameter values in manual operation
Actuators
Parameter values
0
1
2
3
101
1–100
Valve (2-point control)
Off
ON
–
Automatic
–
–
Valve (3-point control)
Closed
Open
Stop
Automatic
–
–
Valve (continuous control)
0 %
–
–
–
Automatic
0–100 %
Pump (2-point control)
Off
ON
–
Automatic
–
–
Demand contact
Off
–
–
–
–
–
8.3.9 Screed drying
Screed drying is used to support the hardening (drying) of a cement floor, where underfloor
heating is embedded. The required steps of the "heating programme" must be specified by
a professional screed installing company. Depending on the flooring material used and the
composition, adjustments must be made in the parameters for starting temperature, heating,
holding and cooling steps before activating the function.
The
screed drying
function is only available in the menu structure, if a feed temperature sensor
is assigned in the heating circuit or the system diagram
50090
is loaded (1 heat pump, control
via communication, 1 heating circuit unmixed without pump). After loading the system diagram,
the
screed drying
function is shown directly on the display.
The function can be activated during operation if another system-specific diagram is loaded.