Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
The function is activated after setting the
type-Pv
parameter and assigning the required inputs.
Name
Information text
Unit
St-SP Settings
type-Pv
1: contact 2: output
3: Dyn. output
1 Select type, i.e. reaction to 1: contact
release, 2+3: calculated excess energy
(generated - used), whereby 2: set minDiff-
Cap, 3: dynamic minDiffCap
rel-pv
Release contact
0 Assigning a contact input 17–26
EMngPv
Electric photovoltaic energy
0 Currently generated output; (terminals 25/26
(meter reading kWh) assign
1
^Imp/kWh
Scaling EMngPV
1 Adjust value of impulse (x Imp/kWh) to
meter signal
EMngBuild
Building electric energy
0 Currently generated output; (terminals 25/26
(meter reading kWh) assign
1
^Imp/kWh
Scaling EMngBuild
1 Adjust value of impulse (x Imp/kWh) to
meter signal
minDiffCap
Minimum output difference
kW
2.0 Demand is triggered when the calculated ex-
cess energy exceeds the pre-set difference
minSwOfTm
Minimum off-time of heat pump min
10.0 A renewed triggering of the demand is made
after the expiry of the set time period
dem-DHW
Loading domestic hot water
1 Setpoint influence 1: yes, 0: no
dem-DHW
Domestic hot water demand
°C
50 Setpoint to which the domestic hot water
tank should be raised during excess energy
dem-HC
Buffer loading heating
1 Setpoint influence 1: yes, 0: no
dem-HC
Demand
Buffer temperature heating
°C
50 Setpoint to which the buffer (heating) should
be raised
dem-cooling
Buffer loading cooling
1 Setpoint influence 1: yes, 0: no
dem-cooling
Buffer temperature demand
cooling
°C
12 Setpoint to which the buffer (cooling) should
be cooled down
boost-hCu
Heating circuits boost
K
0.0 Heating characteristics base point lifted by
0 - 5°K
Lower cooling
Heating circuit lowering
K
0.0 During cooling operation, the SP-cool is
decreased by 0 - 5°K