Commissioning
8
Parameters available for the easy setup
The parameters provided in the following tables are available for the easy setup.
These parameter are only shown, if the
easySetup = 1
parameter is set. These parameter are
not shown, if the
easySetup = 0
parameters are set.
Which parameter is shown depends on which system diagram has been selected and which
heat pump types are indicated. Customized settings are automatically applied after the initial
loading of the system diagram via
cold start = 1
for the parameter of the respective control
circuit.
Explanation for the tables
Name:
Short term for parameter
Information text: Long term of parameters
Unit:
Measuring unit for the parameter
St-SP:
Ex-works set standard setpoint for the parameter
Min.:
Minimum value for the parameter
Max.:
Maximum value for the parameter
Remark:
further information about the parameter
Heat pumps 1 to 3
Name
Information text
Unit
St-SP Min.
Max. Remark
Heat pump 1
maxSP
max. setpoint
°C
70.0
30.0
90.0 Setpoint limitation
boost.hCu
Heating circuits boost
°C
0.0
0.0
10.0 Increase of demand (heat/cool)
BoosterH
Domestic hot water electric
heating element
0
0
1 available 0: no; 1: yes
BoostDel
Time delay domestic hot water
E-heat
min
60
20
95 Switch on delay for the domestic hot water
e-heating element
Cooling
Cooling mode
0
0
1 1: Cooling operation permitted (only genera-
tion “F”)
pumpRotRate
Pump rotation speed
4
0
7 (only generation “F”)
Cooling
Cooling demand via heat pump
release
0
0
1 0: no 1: yes
CAPRAN-WP1
–
–
–
D03
X16 only on All in One models (type-HP1=ADCx):
set the type and performance of the outdoor
unit; D03/05/07/09/12/16: High Performance
range, X09/12/16: T-CAP range
Heat pump 2
see heat pump 1
Heat pump 3
see heat pump 1