Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
Procedure:
►
Starting from the basic display: Press the
[OK]
button to open the menu
structure.
►
Using the
[▼]
button in the
MCR-BMS
menu, select the
domestic hot water
sub-menu.
► Confirm using the
[OK]
button.
►
Using the
[▼]
button, select the
Setpoints
menu.
► Confirm using the
[OK]
button.
The parameter for the occupation times (
SP-OTx
), the non-occupation times
(
SP-NO
) and the special non-occupation times (
SP-SNOT
) are displayed and
can be adjusted, if required.
Name
Information text
Remark
SP-OT1
Setpoint OT1
Standard setpoint: 45.0 °C
SP-OT2
Setpoint OT2
Standard setpoint: 45.0 °C
SP-OT3
Setpoint OT3
Standard setpoint: 45.0 °C
SP-OT4
Setpoint OT4
Standard setpoint: 45.0 °C
SP-NO
Setpoint NO
Standard setpoint: 2.0 °C
SP-SNOT
Setpoint SNOT
Standard setpoint: 2.0 °C
boostDHWflow
Tank flow setpoint boost
Standard setpoint: 0.0 K
boostLoadFl
Loading flow setpoint boost
Standard setpoint: 0.0 K
boostLoadFl
Loading flow setpoint boost
Standard setpoint: 0.0 K
SP-DHWta
Setpoint DHWtank
SP-DHWflow
Controller setpoint
SP-loadFl
Controller setpoint
8.3.5 Heat Circuits – Setpoints, Heat Characteristic, Setpoint
Limitation
After loading of the system diagram, both heating circuits are (if any) the parameters for the
weather-dependent calculation of the feed temperature on a heating system with underfloor
heating are set. Here, a flat heat characteristic curve (gradient /slope:
hCu-slope= 0.5
), a
low curvature (heater element exponent:
hCu-exp = 1,10
) and a comfortable base point
(
RoomOTx = 22 °C
) are saved.
If required, these parameter can be adjusted in the
Heating circuits » Heating circuit x »
Setpoints
.